Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manuel - Page 34

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA. Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA 38 pages. Digital output module
Également pour Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA : Manuel de l'équipement (36 pages)

Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manuel
Drivers, parameters, diagnostics messages and address space
A.2 Parameters, diagnostics messages and address space without PCS 7
The following figure shows the configuration of the channel parameters for channels 0 to 31.
x = 12 + (channel number * 2); with channel number = 0...31
All unused bits and the bits or bytes marked as "reserved" must be set to zero.
You activate a channel parameter by setting the corresponding bit to "1" or the corresponding
value.
Figure A-3
A.2.3

Diagnostics messages and maintenance events

Diagnostics messages
A diagnostics message is generated for each diagnostics event and the DIAG LED on the I/O
module flashes red or the MT LED lights up yellow.
The diagnostics messages can be read in the diagnostics buffer of the CPU.
Diagnostic messages are assigned either channel-specific to an output or assigned as module
messages to all outputs. All channels are switched off for diagnostics messages that affect the
entire module. Only the corresponding digital output is affected by diagnostics messages,
which refer to individual channels.
Table A-1
Diagnostics messages, their meanings and remedy options
Diagnostics
Error code
message
Parameter as‐
10
H
signment error
Supply voltage
11
H
missing
34
Configuration byte x and x+1 for the channels 0 to 31
Assign‐
Meaning
ment
Module
● Parameter assignment does not match
the terminal block used
● Incorrect parameter assignment
Module
Supply voltage L+ missing or too low
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
Remedy
● Correct the parameter
assignment
● Check terminal block
● Check wiring of the supply
voltage at the terminal block
● Check terminal block type
Manual, 09/2018, A5E39265993-AA