The electronic module EM 4 IO-Link HF in combination with the connection module
CM IO-Link 4×M12P has the following technical properties:
● IO-Link master according to IO-Link Specification V1.1
● Dimensions 45 x 130 mm
● 4 IO-Link ports (Port Class B)
● 4 M12 connections
● SIO mode (standard IO mode)
● Supported data transmission rates:
– COM1 (4.8 kBd)
– COM2 (38.4 kBd)
– COM3 (230.4 kBd)
● Configuration limits:
– Max. 32 bytes input data and 32 bytes output data per port
– Max. 32 bytes input data and 32 bytes output data per module
● Automatic backup of device parameters during replacement of the IO-Link device (only
for V1.1 devices)
● Suitable for connection of IO-Link devices with 3-wire and 5-wire connection
● Configurable diagnostics can be set for each port (in IO-Link mode)
The module supports the following functions:
Table 2- 1
Function
Firmware update
Master backup with function block "IO_LINK_MASTER"
IO-Link port configuration with S7-PCT (as of V3.4 Hotfix 1)
IO-Link port configuration without S7-PCT (as of V3.5 Update 1)
PortQualifierInformation (PQI)
IO-Link Master (6ES7147-4JD00-0AB0)
Manual, 03/2018, A5E37967003-AB
Version dependencies of the module functions
Product overview
2.1 Properties
Firmware version of the mod-
ule
V1.0 or higher
V1.0 or higher
V1.0 or higher
V1.1 or higher
V1.1 or higher
11