Également pour Siemens SIMATIC NET : Manuel d'utilisation (29 pages), Manuel d'utilisation (50 pages), Manuel d'utilisation (28 pages), Manuel d'instructions de montage (6 pages), Informations sur le produit (6 pages), Manuel d'installation (40 pages), Manuel d'installation (50 pages), Manuel de référence (14 pages), Manuel d'installation (34 pages), Manuel d'installation (48 pages), Manuel d'utilisation (32 pages)

Siemens SIMATIC NET Manuel d'installation
Certification
6.2 EMC and Environmental Type Tests
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RMC30 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
61000-4-2
61000-4-3
61000-4-4
61000-4-5
61000-4-6
61000-4-8
61000-4-29
61000-4-11
IEC 60255-5
28
Test
IEC
ESD
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Dielectric Strength
Description
Enclosure
Contact
Enclosure Air
Enclosure
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m continuous,
1000 A/m for 1 s
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2 kV  (Fail-Safe
Relay output)
1.5 kV
2 kV
Installation Manual, 04/2021, C79000-G8976-1008-10
Severity
Levels
4
4
a
Note
a
Note
4
4
4
4
3
4
3
3
3
3
a
Note
5
 
 
 
 
 
 
RUGGEDCOM RMC30