Également pour Siemens SINAMICS G120 : Pour commencer (46 pages), Manuel d'utilisation (32 pages), Pour commencer (30 pages), Instructions pour l'installation du matériel (2 pages), Instructions d'installation et manuel du propriétaire (2 pages), Instructions d'installation (2 pages), Instructions d'installation (2 pages), Mode d'emploi Compact (32 pages), Manuel (42 pages), Pour commencer (50 pages), Manuel de l'appareil (34 pages), Manuel d'installation rapide (2 pages), Mode d'emploi Compact (2 pages), Manuel (31 pages), Manuel d'application (34 pages), Mode d'emploi Compact (2 pages), Mode d'emploi Compact (2 pages)

Siemens SINAMICS G120 Description de l'application
4 Configuration and Project Engineering
4.1 Creating the project configuration
No.
Action
16.
The wizard is self-
explanatory.
Enter your motor data here.
Make sure that the same
telegram as in the previous
step is selected at this point.
A summary is displayed
before you complete the
parameterization with
"Finish". This summary can
be backed up using copy and
paste.
The parameterization in the application example is shown below:
Drive setting:
IEC/NEMA mot stds: [0] IEC-Motor (50 Hz, SI units)
Power unit application: [0] Load duty cycle with high overload for vector drives
Motor:
Motor type selection: [1] Induction motor (rotating)
Number of motors connected in parallel: 1
Rated motor voltage: 400 Vrms
Rated motor current: 0.56 Arms
Rated motor power: 18.00 kW
Rated motor power factor: 0.770
Rated motor frequency: 50.00 Hz
Rated motor speed: 1350.0 rpm
Motor cooling type: [0] Non-ventilated
Motion control configuration:
PROFIdrive PZD telegram selection: [1] Standard telegram 1, PZD-2/2
Reference speed reference frequency: 3000.00
Data sets:
DDS: 0
CDS: 0
Open-loop/closed-loop control type:
Open-loop/closed-loop control operating mode: [0] U/f control with linear characteristic
Defaults of the setpoints/command sources:
Macro drive unit: [7] Fieldbus with data set changeover
Important parameters:
Current limit: 0.84 Arms
Minimum speed: 0.000 rpm
Maximum speed: 1500.000 rpm
Ramp-function generator ramp-up time: 0.000 s
Ramp-function generator ramp-down time: 0.000 s
OFF3 ramp-down time: 0.000 s
Drive functions:
Motor data identification and rotating measurement: [0] Inhibited
Automatic calculation motor/control parameters: [1] Complete calculation
SINAMICS G120 as a Speed Axis on the S7-1500
V1.0a, Entry ID: 78788716
Picture
22