Également pour Siemens SINAMICS G120P : Manuel d'utilisation (28 pages), Manuel d'utilisation (26 pages), Manuel d'utilisation (24 pages), Manuel d'utilisation (22 pages), Manuel d'utilisation (26 pages), Manuel d'utilisation (22 pages), Manuel d'utilisation (22 pages), Manuel (18 pages), Manuel d'utilisation (18 pages)

Siemens SINAMICS G120P Manuel d'utilisation
Electrical installation
Cable cross-sections
For du/dt filters with separate Voltage Peak Limiter (Article Nos. 6SL3000-2DE41-4EA0 and
6SL3000-2DG38-1EA0) the connections between du/dt reactor and Voltage Peak Limiter are
already attached to the Voltage Peak Limiter.
Table 4- 1
Article numbers 6SL3000-2DE41-4EA0 and 6SL3000-2DG38-
Table 4- 2
2DE41-4EA0 and 6SL3000-
Risk of fire due to ground fault/short-circuit
Inadequate installation of the cables to the Power Module compact DC link can result in a
ground fault/short-circuit and place persons at risk as a result of the associated smoke and
fire.
• Use the local installation regulations to avoid this fault.
• Protect the cables against mechanical damage.
• Also implement one of the following measures:
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m). Use an
equivalent cable type when replacing the cables supplied.
24
Cable cross-sections for connections between a du/dt filter and Power Module
du/dt filter compact plus Voltage Peak Limiter
Article No. 6SL3000-2DE35-0EA0
Article No. 6SL3000-2DE38-4EA0
Connection cable enclosed for connecting dv/dt reactor and Voltage Peak Limiter
Voltage Peak Limiter
Article numbers 6SL3000-
2DG38-1EA0
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
1EA0
Cross-section
[mm²]
70
Cross-section
[mm²]
Lug for connecting 1U2 / 1V2 /
1W2 on the dv/dt reactor
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC
25
50
95
M12