Siemens SINAMICS G130 Manuel d'utilisation - Page 13

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Siemens SINAMICS G130. Siemens SINAMICS G130 46 pages. Line filter
Également pour Siemens SINAMICS G130 : Manuel d'utilisation (24 pages), Manuel d'utilisation (26 pages), Manuel d'utilisation (46 pages), Manuel d'utilisation (24 pages), Manuel d'utilisation (31 pages), Manuel d'utilisation (30 pages), Manuel d'utilisation (28 pages), Manuel d'utilisation (30 pages), Manuel d'utilisation (22 pages), Manuel d'utilisation (28 pages), Manuel d'utilisation (30 pages), Manuel d'utilisation (34 pages), Manuel d'utilisation (26 pages), Manuel d'utilisation (26 pages), Manuel d'utilisation (28 pages), Manuel d'utilisation (42 pages), Manuel d'utilisation (46 pages), Manuel d'utilisation (24 pages), Manuel d'utilisation (24 pages), Manuel d'utilisation (30 pages), Manuel d'utilisation (42 pages), Manuel d'utilisation (38 pages), Manuel d'utilisation (46 pages), Manuel d'utilisation (28 pages), Manuel d'utilisation (22 pages), Manuel d'utilisation (24 pages)

Siemens SINAMICS G130 Manuel d'utilisation

General

Description
The dv/dt filter plus voltage peak limiter comprises two components: the dv/dt reactor and
the Voltage Peak Limiter, which cuts off the voltage peaks and returns the energy to the DC
link.
The dv/dt filters plus Voltage Peak Limiter must be used for motors for which the proof
voltage of the insulation system is unknown or insufficient.
dv/dt filters plus Voltage Peak Limiters limit the rate of voltage rise to values < 500 V/µs and
the typical voltage peaks with rated line voltages to the values below:
< 1000 V at U
< 1250 V at 660 V < U
Danger to life if the fundamental safety instructions and remaining risks are not carefully
observed
The non-observance of the fundamental safety instructions and residual risks stated in
Chapter 1 can result in accidents with severe injuries or death.
• Adhere to the fundamental safety instructions.
• When assessing the risk, take into account residual risks.
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. This can also result in increased failures and reduced service
lives of braking resistors.
• Maintain 100 mm ventilation clearances above and below the component.
Risk of burns due to high surface temperature of the dv/dt reactor
The surface temperature of the dv/dt reactors may exceed 80° C. You can get seriously
burnt when touching the surface.
• Mount the dv/dt reactor so that it cannot be touched. If this is not possible, attach a
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E00692302A
< 575 V
line
< 690 V.
line
WARNING
WARNING
CAUTION
clearly visible and understandable warning notice at hazardous positions.
2
13