Commissioning

5.1

Start up

1. With the SITRANS LU180 correctly installed (or aimed at a wall 0.25 to 5 m away), apply
power.
The device starts up, displaying the following:
2. It then defaults to the Run mode, which is the measurement reading of the distance from
the transducer face to the material level in the units indicated as shown:
3. If the default display differs from that shown, refer to SITRANS LU180.
SITRANS LU180
Operating Instructions, 09/2021, A5E37100674-AB
'4' key
'20' key
Program mode
Alphanumeric
Units
LOE/fault
Operation status
5