Siemens 125-1957 Manuel du propriétaire - Page 13

Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Siemens 125-1957. Siemens 125-1957 48 pages. Apogee unit vent controller ⎯ 0 to 10v output

Hardware Outputs

Analog (0 to 10V)
Cooling valve actuator
Face-bypass damper actuator
Heating valve actuator
Outdoor air damper actuator
Digital
Auxiliary radiation electric coil contact; or,
auxiliary radiation two-position valve actuator
Unit fan
First stage electric heat
Second stage electric heat
Third stage electric heat
Two-position cooling valve actuator
Two-position heating valve actuator
DX coil

Power Wiring

The controller is powered by 24 Vac and connects to the two screw terminals on the
controller. Labeled "C" (Common) and "H" (Hot) on the terminal block labeled "24 VAC". No
earth-ground connection is required (Figure 2).

Communication Wiring

The controller connects to the field panel by means of a Floor Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled "+"
(positive), "-" (negative), and "S" (Shield) (Figure 3).
Siemens Building Technologies, Inc.
Application
2281, 2283, 2287
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286, 2287
2281, 2283, 2284, 2286
Application
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286, 2287
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286
2284, 2286, 2287
Introduction
3