Siemens 550-507 Manuel d'instructions d'installation - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} Siemens 550-507. Siemens 550-507 9 pages. Ce compliant dual duct controller -two air velocity sensors -electronic output
Document Number 550-308
Installation Instructions
Rev. 1, July, 2001
COVER
24 V-AC
C H GND
C H E
POWER
TRUNK
TERMINATIONS
Figure 1. CE Compliant Dual Duct Controller — Two Air Velocity Sensors without Autozero Modules.
New Installation Instructions
1.
Using the mounting rail as a template (Figure
1), mark the screw holes where you will install
the controller assembly.
2. Do one of the following:
•
If using the self-tapping screws provided:
Using the drill and the hex nut bit, fasten the
mounting rail.
•
If not using the self-tapping screws: Drill
two 1/8-inch (3 mm) pilot holes, then fasten
the mounting rail with No. 6 or No. 8 screws.
3. Place the ESD wrist strap on your wrist and
attach it to a good earth ground.
4. Carefully remove the controller assembly from
the anti-static bag. Center it over the mounting
rail and snap it securely into place.
5. Connect the Floor Level Network (FLN). See
Figure 4.
6. Connect the point wiring as shown in Figure 7.
NOTE: Wiring to DI3/AI3 requires a clamp-on
ferrite filter (Figure 6). Strain relief must be
provided to ensure long-term effectiveness
due to added weight of the filter.
Page 2 of 9
DO1
DO2
DO3
DO4
DO5
DO7
DO6
NO C
NO C
NO C
NO C
NO C
NO C
NO C
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
DO LEDS
INPUT / OUTPUT TERMINATIONS
AIR VELOCITY
SENSOR PORTS
HI
LO
DI3
DO8
DI2
AI3
BST
BST LED
NOTES: 1. Each DO provides a Normally Open (NO)
2. The 24 Vac "H" terminal is switched
7. If using Autozero Modules, refer to the
Installation Instructions (540-199), which are
included.
8. After the Autozero Modules are installed,
connect the Autozero Module wires to the
controller at DO7.
LO
HI
FLN TRUNK
+ - S
RX TX
RTS
+ - S
FLN
ROOM TEMPERATURE
TRUNK
SENSOR / MMI PORT
TERMINATIONS
TRANSMIT LED
RECEIVE LED
CAUTION:
The Controller's Digital Outputs (DOs)
control 24 Vac loads only. The maximum
rating is 12 VA for each DO. Use an
interposing 220V 4-relay module for any of
the following:
•
VA requirements higher than
maximum.
•
110 or 220 Vac.
•
DC power.
•
Separate transformers used to
power the load.
and a Common (C) terminal. Terminate
both connections of a 24 Vac load directly
to the controller board. Actuators use two
DOs and require three connections.
through a TRIAC to the NO terminations
when the associated DO is energized.
Siemens Building Technologies, Inc.
CONTROLLER
BOARD
MOUNTING
HOLE
(2)
MOUNTING
RAIL