Siemens XC10 Series Fonctionnement - Page 21

Parcourez en ligne ou téléchargez le pdf Fonctionnement pour {nom_de_la_catégorie} Siemens XC10 Series. Siemens XC10 Series 32 pages. Extinguishing control unit

Siemens XC10 Series Fonctionnement
Building Technologies
Fire Safety
At this stage, no action can be carried out to prevent extinguishing release. All
people in the area to be flooded must immediately evacuate it. However, you have
the option of temporary hold or abort extinguishing (only a local intervention,
provided this device is installed).
1. Press the Emergency Hold Button, until all people have left the room or press
the Emergency Abort Button, if you want to abort the initiated extinguishing
Flooding Time
The extinguishing actuator is triggered after pre-warning time elapsing and flooding
time beginning.
-
the red Led "Activated" is on (continuous)
-
after several seconds the alarm horn changes to continuous sound
-
the pressure switch reports the released condition of the extinguishing agents,
then the red Led "Released" is activated
You can now silence the alarm horn:
1. Enable operating access level 2 (access code or key)
2. Press the "Silence Re-sound Horn" (5) key
Note: Horn silence is only accepted after state "Released" is reported
Released condition is shown as soon as actuators are triggered or after
"extinguishing agent release" contact as been activated (if this contact is used).
Reset
After the flooding time (adjustable from 1 to 30mn - 1mn by default), you can reset
the control unit by pressing the « Reset » key (7).
The reset can be only carried out after flooding time elapsed, internal buzzer and
sounders silenced, discharged contact restored and manual release button
restored (if it was actuated).
Fire Controls
In the event of "Fire alarm" or "Activated", different building services have been
included in the defined fire position. These can be set back to their normal
operating states after successful extinguishing and resetting the system.
Remote Transmission
If the extinguishing control unit is connected to remote transmission device, then it
is activated as a rule only in the event of "Activated" or "Released" conditions.
If the extinguishing control unit is connected to a fire detecting system, then as a
rule "Fire alarm", "Activated" and "Released" conditions are forwarded.
Operation
21
A6V10257477_c_en_--
2012-06