Siemens SKB60 Manuel - Page 7
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SKB60. Siemens SKB60 32 pages. Auxiliary switch
Également pour Siemens SKB60 : Instructions de montage (6 pages), Instructions de montage (10 pages), Instructions de montage (7 pages), Instructions de montage (6 pages), Instructions de montage (10 pages), Instructions de montage (4 pages)
The LED on the SKB62/MO cable adapter flashes red during the calibration, as the
positioning signal Y and the positioning feedback U do not correspond anymore. This is
interpreted as a blockage and thus indicated as an error.
If necessary, the calibration can be repeated any number of times.
LED indication of operational status
SKB60, SKB62.., SKB62/MO
The dual-colored LED indicating the operational status is visible when the cover is removed.
LED
indication
Lit green
Flashing green
Lit red
Flashing red
As a general rule, the LED can only assume the states shown above – continuously lit red or
green, flashing red or green, or off/dark.
Siemens
Smart Infrastructure
Function
Normal operation
Stroke calibration in progress
Faulty stroke calibration
Internal error
Inner valve jammed
No power supply
Dark
Electronics faulty
Remarks, troubleshooting
Automatic operation; everything o.k.
Wait until calibration is finished
(LED stops flashing, will be lit green or red)
Check mounting; restart stroke calibration (by short-circuiting
calibration slot)
Replace electronics
Troubleshoot, check valve, restart stroke calibration
Check mains network, check wiring
Replace electronics
7
CM1N4564en
2023-10-17