Bitzer BDC 380 (5F) (V) Manuel d'utilisation - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Bitzer BDC 380 (5F) (V). Bitzer BDC 380 (5F) (V) 10 pages. Bdc series air cooled condensers

Insertion of any object into condenser fans is to be avoided as this may result in personal injury and/or
equipment damage.
Operating sound pressure levels may cause discomfort. Refer to catalogue for calculated sound levels
3.

Application Ranges

These condensers are intended for use in commercial refrigeration systems with a maximum operating
ambient temperature of approximately 60°C (special designs available on application).
Recommended refrigerants: HFCs, HCFCs (also suitable for CFCs).
This series of condenser is not suitable for use with NH3 (Ammonia), R410a or R744 (CO2).
Standard condensers are not to be installed in hazardous/combustible environments.
4.

Installation Guide

The BDC Series of Air Cooled Condensers are suitable for Vertical and Horizontal air flow.
a)
Mounting - Vertical Air Flow
Remove the condenser from its crate.
Vertical air flow condensers are shipped without legs fitted.
Legs are supplied within each BDC Series condenser crate.
Using an appropriate lifting device (refer Figure 1 for recommended lifting methods), attach the
legs to the condenser using the bolt kit supplied.
Place the condenser into the installation position and secure using the mounting holes located in
the legs.
b)
Mounting - Horizontal Air Flow
Remove the condenser from its crate.
Horizontal airflow condensers are shipped with mounting feet fitted in final position.
Using an appropriate lifting device (refer Figure 2 for recommended lifting methods).
Place the condenser into the installation position and secure using the mounting holes located in
the feet.
NOTE:
Minimum diameter of fixing bolts is to be 12.70mm (½")
The use of lifting devices during installation is recommended where applicable
Observe recommended condenser mounting locations as per Figure 2.1, parts 1 and 2
Remove the transport brackets from the BDC Series condensers (vertical only)
Ensure the condenser is installed level, to avoid liquid locking within the condenser
Refrigeration piping connections should be carried out in accordance with the current Refrigeration
Code of Good Practice* (beware of HOT surfaces present during the welding procedure).