Digital Lumens RLE Series Manuel d'instructions d'installation - Page 4

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} Digital Lumens RLE Series. Digital Lumens RLE Series 8 pages.
Également pour Digital Lumens RLE Series : Manuel d'instructions d'installation (20 pages)

RLE

INSTALLATION INSTRUCTIONS

GETTING STARTED

1: Verify Optic Type
Use optic type specified in the project plan — WIDE or NARROW.
Hint:
The optic type is printed on the fixture label
2: Add Tracking Labels to Sticker Book
Detach plastic bag from fixture, then remove product and controller
barcode label assembly from bag and affix to sticker book, as depicting
the intended installation location of the fixture
3: Rotate Light Bars
a. Rotate the lightbars into position as specified in the project plan
(Illustration 3)
.
Note:
Ensure at the light bar release buttons are secured within
the appropriate detents.
Note:
Refer to Appendix B for typical lightbar positioning examples.
4: Install Fixtures
Note:
Fixture must be positioned at least 0.2m (8 in) from the ceiling.
Note:
Fastening hardware supplied by installer.
Option 2a: Aircraft Cable – RLE-D1/H1
a. Refer to the sticker book to confirm the correct location and
placement of the fixture.
b. Secure aircraft cable to a beam or truss.
c. Connect cable to fixture housing using aircraft cable hanging
hardware
.
(Illustration 4e)
d. Use a box level to level the fixture.
Hint:
For aisle illumination, verify that fixture is oriented correctly
.
(Illustration 4f)
Option 2b: Aircraft Cable – RLE-P1
a. Refer to the sticker book to confirm the correct location and
placement of the fixture.
b. Secure aircraft cable to a beam or truss.
c. Connect cable to fixture housing using aircraft cable hanging
hardware
(Illustration 4g)
.
d. Use a box level to level the fixture.
Hint:
For aisle illumination, verify that fixture is oriented correctly
.
Illustration 4h)
Product Ratings
!
RLE-D1-ST: 120-277 V AC, 50/60 Hz, 145 W (max), 1.21 A (max)
RLE-H1-ST: 120-277 V AC, 50/60 Hz, 214 W (max), 1.79 A (max)
RLE-P1-ST: 120-277 V AC, 50/60 Hz, 428 W (max), 3.56 A (max)
4
5: Make Electrical Connections
Suitable for cords 1.5mm
.
(Illustration 1)
e. Remove (2x) Phillips
f. Extract the internal three-wire bundle from wiring compartment
.
(Illustration 2)
g. Connect external wiring to internal wire bundle using supplied
h. Use supplied cable gland or suitable IP-rated wiring connector
i. Replace wiring compartment access panel and tighten screws to
6: Verify Sticker Book
To prevent issues during commissioning, ensure that the placement
of the bar code label in the sticker book corresponds to the fixture's
physical location in the facility.
RLE-D1-HV: 347-480 V AC, 50/60 Hz, 148 W (max), 0.43 A (max)
RLE-H1-HV: 347-480 V AC, 50/60 Hz, 217 W (max), 0.63 A (max)
RLE-P1-HV: 347-480 V AC, 50/60 Hz, 434 W (max), 1.25 A (max)
–2.5mm
2
Do not connect or disconnect while under load.
screws retaining the wiring compartment
®
access panel
(Illustration 5a).
and identify the wire leads
(Illustration 5b)
WAGO splicing connectors
(Illustration 5d).
(supplied by installer) to route power cable through access panel
(Illustration 5e)
.
8 kgf-cm
.
(Illustration 5f)
2