ActronAir MGW-CLDCS Manuel d'utilisation - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} ActronAir MGW-CLDCS. ActronAir MGW-CLDCS 12 pages. Vrf cloud gateway

2.2.2 Restore Factory Settings
Function
When the factory configuration is restored, the gateway IP address, and server parameters are set
to factory setting values.
Steps:
1. Power off the Gateway, press and hold SW1 and turn on the power of Gateway;
2. Keep holding SW1 until the digital display shows "LL" and release SW1; when the digital display
shows "FF", the Gateway has been restored to factory configuration and automatically reset and
restarted.
2.2.3 Emergency Stop
In the event of a short circuit connection of DI1 and M, the Gateway will start the emergency
shutdown function.
Logic description of emergency stop: The Gateway uses continuous polling (*4) to obtain the
information of the connected device. During the effective period of the emergency stop function,
the Gateway determines that the IDU is locked in the on state according to the polling information,
and will unlock the locked-on attribute of the corresponding IDU.
If the IDU is on, the Gateway sends a shutdown command until the Gateway exits the emergency
stop function (*5).
*4: The interval of Gateway polling depends on the number of devices connected, and usually
takes five minutes to complete.
*5: Exiting the emergency stop will not restore the IDU's locked-on status, namely, the IDU which
was originally locked on becomes unlocked.
SW1
Restore Factory Configuration
07
SW2
Reserved