Actulux HCVA 500/600 Manuel d'instructions - Page 4

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions pour {nom_de_la_catégorie} Actulux HCVA 500/600. Actulux HCVA 500/600 12 pages. Chain drive

Actulux HCVA 500/600 Manuel d'instructions
HCVA/HCVAR

Features

- Microprocessor controlled Bus synchronization.
- HCVAR is incl. remote control
- Max. 4 pcs. drives can be synchronized.
(1 pcs. HCVAR can be synchronized with up to 3 pcs. HCVA, but max. 1 pcs. HCVAR per
synchro set)
- Push / Pulling, Opening / Closing Speed and Stroke length can be programmed.
- Electronic overload protection.
- Reduced speed and force during the last 50 mm of closing ("Soft-close").
- Drive is supplied with 2.5 m silicone cable.
- Different types of brackets can be mounted, depending on the window and kind of mounting.
- Tested in accordance with EN 12101-2, EN 50130-4.

Technical data

Type
HCVA/R 500/350
HCVA/R 500/600
HCVA/R 500/800
HCVA/R 500/1000
- Power supply: 190-250 VAC / 50 Hz Max 10A
- Consumption: 0.5A/230 VAC
- Inrush current: 45A/230 VAC
- Leakage current: <0,25mA / 240 VAC
- Speed open/close: 7 mm/s
- Soft close speed: 5 mm/s
- Soft close distance: 50 mm
- Soft close force: 200 N

Dimensions for type HCVA

Stroke
Lenght L
350 mm
586 mm
600 mm
711 mm
800 mm
811 mm
1000 mm
916 mm
Length of antenna (HCVAR) 35 mm
Voltage /
Pushing
Current
force
230VAC/25W
500N
230VAC/30W
500N
230VAC/30W
500N
230VAC/30W
500N
Pulling
Stroke
force
length
500N
350 mm
500N
600 mm
500N
800 mm
500N
1000 mm
- Protective class: IP32
- Temperature range: -25°C ~ +75°C
- Locking force: 2000 N
- Lifecycle: >11000 double strokes
- Duty cycle: 30% at 10 min. running time
4
Speed
Natural comfort
7 mm/s
7 mm/s
10 mm/s
10 mm/s