Argina CM+ Manuel d'instructions d'installation - Page 13

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} Argina CM+. Argina CM+ 20 pages. Conventional fire alarm control panel

13 Configuring using the operating panel

The fire alarm control panel is configured according to local needs during commissioning.
The basic configuration can be set up using the operating panel.
!!
This may only be done by specialist technicians.
The CMPlus.exe program is required for full configuration.

13.1 Available functions

function 1
function 2
function 3
function 4
function 5
function 6
function 7

13.2 Selecting the desired function

Press the 'lamp test' key and hold it in for 5 seconds to open the selection menu for the available
functions.
The alarm LEDs for all the available functions flash in this selection menu. Each alarm LED
corresponds to a function: zone 1 alarm LED = function 1, zone 2 alarm LED = function 2, etc.
Press the zone key to select the desired function.
The Installer Code has to be entered after the desired function has been selected. (the Enter
Code LED flashes). The function becomes active only when the correct code has been entered.
The functions can be accessed for 2 minutes after the code has been entered.
If no key is pressed for 20 seconds, the normal indications are displayed again.

13.3 Delay times T1, T2, T3 (Functions 1, 2, 3)

Delay time operation in the day scheme
The Delayed Operation LED is on in this operation mode.
delay time T1: ... minutes = Operator Response Time
delay time T2: ... minutes = Inspection Walk Time
siren operating time T3: ... minutes
In the event of an alarm, the general alarm LED and the LED for the zone in which the alarm
was detected come on. The control panel buzzer sounds a continuous tone. Operator Response
Time T1 starts running at this point.
If no action is carried out on the operating panel, all alarm devices will be activated after a delay
time of T1. The siren operating time T3 starts running at this point. This condition is shown on
the operating panel by the Alarm Routing LED lighting. The alarm devices stop automatically
when this delay time has elapsed See time diagram a: no operator response.
If the Buzzer Stop key on the operating panel is pressed within delay time T1, time T1 stops and
inspection walk time T2 starts. This is the time allowed to investigate whether evacuation is
necessary.
First delay time T1 (Operator Response Time)
Second delay time T2 (Inspection Walk Time)
Siren Operating Time T3
Zone set-up: immediate / delayed alarm
Show alarm counter
User Code
Installer Code