Argo ADIBS13DC Manuel d'instructions d'installation - Page 13
Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} Argo ADIBS13DC. Argo ADIBS13DC 19 pages. Split air conditioner system
Également pour Argo ADIBS13DC : Manuel d'utilisation (15 pages), Manuel d'utilisation (17 pages)
17 - OUTDOOR/INDOOR UNIT REFRIGERANT CIRCUIT ADDRESS
Indoor units that are part of a multisplit system must be properly configured to be able to communicate with the
outdoor unit over different channels (Indoor A, Indoor B, etc...) of the communication bus.
Each indoor unit address must correspond to the physical connection of the indoor unit to the outdoor unit refrigerant
circuit, i.e.:
Refrigerant Circuit A <--> Indoor Unit Address A
Refrigerant Circuit B <--> Indoor Unit Address B
...
There are three methods to set the address of an indoor unit:
(1) Dip-switch setting: the address is set by mean of a dip-switch located on the indoor unit pcb.
(2) Remote controller procedure: the address is set by mean of a special setting on the remote controller.
(3) Automatic addressing procedure: the address is automatically set on every indoor unit of the system by mean of
an automatic procedure.
(1) ADDRESS SETTING THROUGH DIP-SWITCHES (UP TO 4 INDOOR UNITS)
Disconnect the power
Check that the setting of switch SW2 (PCB) corresponds to the figure:
INDOOR UNIT A
SW2
(PCB factory state)
1=off
2=off
INDOOR UNIT C
SW2
1=off
2=on
PCB
13
INDOOR UNIT B
SW2
PCB
1=on
2=off
INDOOR UNIT D
SW2
PCB
1=on
2=on
EN