1 - INSTALLATION SITE SELECTION

EN
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur
(such as in kitchen or near factory equipment) because
oil contamination can cause operation problems and may
deform plastic surfaces and parts of the unit.
• Unsteady locations that will cause noise or possible
water leakage.
• Locations where the indoor unit and the remote control
unit will be splashed with water or affected by dampness
or humidity.
• To make holes in areas where electrical wiring or conduits
are located

2 - SYSTEM WIRING DIAGRAM

DILAYED FUSE
220 - 240 V ~ 50 Hz
Main switch for disconnection from the
supply line must have a contact separation
in all poles that provides full disconnection
under category III overvoltage conditions.

3 - WIRES' LENGTH, SIZE AND DELAYED FUSE

SEE INSTALLATION INSTRUCTIONS OF OUTDOOR UNIT
Power supply wire A :
Multipolar electric wire; size and length of the suggested electric wire are showed on table "electrical data"
(Outdoor unit).
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table "electrical data"
(Outdoor unit). The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table "electrical data"
(Outdoor unit). The wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22). Make
sure the length of the conductors between the fixing point and the terminals allows the straining of the conductors
L, N before that of the grounding.
DO
• Select an appropriate position from which every corner
of the room can be uniformily cooled.
• Select a sufficiently strong location to support the weight
of the unit.
• Select a location where tubing and drain hose have the
shortest run to the outside.
• Allow access for operation and maintenance as well as
unrestricted air flow around the unit.
WARNING !
Always connect Phase to L and Neutral to N
DO NOT INVERT THE WIRES, OTHERWISE
THE UNIT MAY NOT WORK PROPERLY.