Argo FCW03 Manuel d'utilisation et d'installation - Page 9

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation et d'installation pour {nom_de_la_catégorie} Argo FCW03. Argo FCW03 20 pages. Fan coil unit wall mounted type

Argo FCW03 Manuel d'utilisation et d'installation

1.3 Working Conditions

(1) The entering water temperature for cooling is suggested to be no less than 5℃ ,otherwise it woule lead
to condensate; the entering water temperature for heating is suggested to be not higher than 60 ℃ ,
otherwise it would lead to corrosion of copper tubes or abnormal noise.
(2) The suggested working environment temperature for cooling ranges 16 ~ 40℃ and ranges 10 ~ 30℃
for heating. Beside, the relative humidity is or less than 80%.
(3) This product is a kind of comfort air conditioning, and is not allowed to be installed where there are
corrosive, explosive and inflammable substances or smog; otherwise it would lead to operation failure,
shortened service life, five hazard or even severe injuries. Special air conditions are required for where
mentioned above.
(4) The A-weighted sound pressure level is below 70dB.
(5) The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
y Cooling capacity: air 27°C DB , 19°C WB, water temperature intake 7°C, outlet 12°C.
y Heating capacity: air 20°C DB , For the tow-row coils applicable to EU, the entering/leaving water
temperature is 45°C and 40°C; and for the four-row coils, the entering/leaving water temperature is
65°C/55°C.
y Freeze-up : air 27°C DB, 24°C WB , water temperature 6°C intake , 10°C outlet .
y Sound power level according to ISO 5151. Sound pressure level are calculated at the below of air-
outlet 1m and 1m distance. The noise are tested before leaving factory.
Fan Coil Unit Wall Mounted Type
30