Distances
• Maintenance operations from FIMER service could entails removing the
front cover. Always observe the required installation safety distances in
order to allow routine check and maintenance operations.
• Provide a sufficient working space in front of the inverter that allows
to removing the front cover (FIMER service only) and to allow wiring
connections.
• Install at a height which takes into consideration the weight of the unit and
in a position which is suitable for servicing, unless suitable means will be
provided to carry out these mentioned operations.
• If possible, install at eye-level so to allow to easily check the:
- synoptic (03).
- display (26). Only in inverter model with ;DISPLAY suffix.
• Do not install any object (e.g. AC or DC cables) that could be damaged
by overheating from outgoing hot air flow coming from top side. In case of
this kind of installation needs, please evaluate the installation of a proper
air deflector. Always respect the minimum distances required.
• Respect the minimum distances from surrounding objects that could
prevent the inverter installation and restrict or block the air flow:
A = 70cm (27")
B = 50cm (20")
C = 20cm (8")
D = 20cm (8")
E = 50cm (20")
A
ATTENTION –
Please check the manual for some particular
A
scenarios that may vary the minimum clearance distances.
Installation of multiple units
• In case of installation of multiple units in the same place, position the
inverter side by side paying attention to keep the minimum clearance
distance G of 30cm/12" (measured from the outer edge of units).
G
If the space available does not allow this arrangement, position the
G
inverters in a staggered arrangement so that heat dissipation is not
affected by other inverters below. Respect the following minimum
clearance distances H of 100cm/39" and I of 30cm/12".
I
I
H
H
ATTENTION –
Please check the product manual for "Wireless
A
signal environmental checks", "Installations at high altitudes" and
"Installations with a high level of humidity".
NOTE –
The final installation of the inverter must not compromise
D
the access to any disconnection devices located outside.
NOTE –
Refer to the warranty conditions to evaluate the possible
D
exclusions related to an improper installation.
B
C
D
E
G
G
H
I
H
I
H
H
G
G
5. Supplied Component list
Component
6. Assembly instructions
Bracket installation
The mounting bracket can be used to install the inverter on a vertical
support.
• Position the mounting bracket (05) perfectly level on the support and use
it as drilling template.
NOTE –
It is the installer's responsibility to choose an appropriate
D
number and distribution of attachment points. The choice must be
based on the type of support (wall, frame or other support), the
type of anchors to be used, and their ability to support 4 times the
inverter's weight (4x29.6Kg/65lbs=118.4Kg/260lbs for all models).
Depending on the type of anchor chosen, drill the required holes (4
minimum) to mount the bracket. Put at least 2 screws in the upper
side and at least 2 in the lower side.
• Attach the bracket (05) to the support.
Vertical mounting bracket (05)
AC quick fit connector (09) +
locking clip
Two-hole gasket (6mm Ø) for
M20 Digital input and RS485
cable gland (20) and cap
Three-hole gasket (6mm Ø)
for M25 Ethernet 1/2 cable
gland (21) and caps
Three-hole gasket (7mm Ø)
for M25 Ethernet 1/2 cable
gland (21) and caps
M6 screw + M6 serrated lock
washers to clamp the earth cable
on the Protective Earth (PE)
external connection point (04)
Eyelet cable lug (16mm
wire)
2
for Protective earth (PE)
external connection point (04)
Digital input and RS485
counterpart (12)
Wireless antenna (14)
M5 screws (with washers) for
mechanically securing the
inverter to the bracket (18)
Technical documentation