Acuity Brands Sensor Switch WSX PDT Manuel de démarrage rapide - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Acuity Brands Sensor Switch WSX PDT. Acuity Brands Sensor Switch WSX PDT 4 pages. Wall switch sensor w / convertible neutral / no neutral wiring, passive infrared (pir) or dual tech (pdt)
COVERAGE PATTERN
• Small motion (e.g., hand movements) detection up to 20 ft (6.10 m), ~625 ft
• Large motion (e.g., walking) detection greater than 36 ft (10.97 m), ~2025 ft
• Wall-to-Wall coverage
• Passive Dual Technology (Microphonics) provides
overlapping detection of human activity over the
complete PIR coverage area. Advanced filtering is
utilized to prevent non-occupant noises from
keeping the lights on.
CONVERSION FROM GROUND ONLY (NO NEUTRAL) TO NEUTRAL WIRING
pre-configured for wiring without a neutral, however if connection to neutral is required by code, contractors can quickly and easily convert the unit in seconds.
This product is
Step 1:
Remove Yellow
Label
WIRING TO GROUND (NO NEUTRAL)
SINGLE RELAY
GND
H
BLK
LOAD 1
BLK
DUAL RELAY
N
H
BLU
LOAD 2
BLU
Sensor Switch 900 Northrop Road, Wallingford, CT 06492 Phone: 1.800.PASSIVE sensorswitch.com ©2013 Acuity Brands Lighting, Inc. All rights reserved 07/01/13
2
2
SIDE VIEW
1.2 m
4 ft
m
0
3
6
0
ft
9
18
Small motion
detection to ~20 ft
Large motion detection to >36 ft
Step 2:
Loosen Screws and
Remove Metal Link
WIRE COLOR KEY
120/277 VAC WIRING
N
BLACK*
- Line 1 Input
BLACK*
- Load 1 Output
BLUE*
- Line 2 Input
BLUE*
- Load 2 Output
347 VAC WIRING (-347 Option)
Red wires replace Black wires.
GND
H
N
BLK
LOAD 1
BLK
Notes:
- Unit will draw power from either line connection.
- Both poles' line connection must be same phase.
20
6
Small
Small
motion
motion
detection
detection
to ~20 ft
10
3
9
12
0 ft
12
0 m
9
6
27
36
36
30
20
Connect Neutral to
Silver Screw and
Ground to Green Screw
WIRING TO NEUTRAL
SINGLE RELAY
}
*BLACK wires
can be reversed
}
*BLUE wires
can be reversed
DUAL RELAY
N
H
BLU
LOAD 2
BLU
WSX Family
TOP VIEW
3
0 m
3
10
0 ft
10
Small motion ~40 ft coverage
Step 3:
N
H
GND
BLK
LOAD 1
BLK
N
H
GND
BLK
LOAD 1
BLK
6
9
12
20
30
36
N
N
3 of 4