ABB DCS800-EP2-0260-05 Manuel du micrologiciel - Page 6
Parcourez en ligne ou téléchargez le pdf Manuel du micrologiciel pour {nom_de_la_catégorie} ABB DCS800-EP2-0260-05. ABB DCS800-EP2-0260-05 20 pages.
6
Terminal #
Signal
Torque Control
90...270 V
1
AITAC-
30...90 V
2
AITAC-
8...30 V
3
AITAC-
4
AITAC+
X3:
5
AI1-
Torque Reference
6
AI1+
7
AI2-
8
AI2+
9
AI3-
10
AI3+
1
AI4-
2
AI4+
3
0 V
4
+10 V
5
-10 V
X4:
6
0 V
7
AO1
Motor speed
8
AO2
Motor torque
9
IACT
Actual motor current
10
0 V
X5:
1-10
1
DI1
Off2 (coast stop)
2
DI2
Speed/Torque select
3
DI3
External fault
4
DI4
X6:
5
DI5
6
DI6
7
DI7
8
DI8
(MainContAck)
9
+24 V
10
0 V
1
DO1
2
DO2
ReadyRef (running)
3
DO3
Fault or alarm
4
DO4
X7:
5
DO5
DC-breaker trip cmd.
6
DO6
7
DO7
8
0 V
1
X96:
DO8 Relay
Main Contact. On
2
DI-2 switches
between speed
and torque control.
W hile in torque
control, AI-1 is
used as reference;
while in speed
control 23.01 is
Description
used as reference.
DO-5 can control
a DC circuit
breaker. Control
is 2-wire.
Table 1b: Macro Configurations: The analog and digital inputs and outputs shown in this table are
automatically configured when you implement the macro identified in the top row.
*New Macro
DCS800 Firmware manual supplement for North America (rev. 2.60, 2.70) Rev. b
Torque Limit*
-
-
-
-
-
-
-
-
Speed Reference
-
Torque Limit
-
-
-
-
-
-
-
-
-
-
-
-
Motor speed
Arm. voltage act.
Actual motor current
-
-
-
-
Jog1
Jog2
External fault
-
External alarm
E-Stop
E-Stop
Reset
Reset
OnOff1
OnOff1
StartStop
StartStop
(MainContAck)
-
-
-
-
ReadyRun
ReadyRun
ReadyRef (running)
Fault or alarm
Zero speed
ZeroSpeed
Above limit
-
-
-
-
-
-
Main Contact. On
Same as
"Standard" except
AI-2 determines
torque limit.
2-Wire DC Contact US*
3-Wire DC Contact US*
-
-
-
-
Speed Reference
Speed Reference
-
-
-
-
-
-
-
Motor speed
Motor speed
Arm. voltage act.
Arm. voltage act.
Actual motor current
Actual motor current
-
-
Jog1
FixedSpeed1
Jog2
External fault
External fault
Main Cont Ack
Main Cont Ack
E-Stop
E-Stop
Reset
Reset
OnOff1
On Start pulse
StartStop
Off1 Stop pulse NC
(MainContAck)
-
-
ReadyRun
ReadyRun
ReadyRef (running)
ReadyRef (running)
Fault or alarm
Fault or alarm
Zero speed
Zero speed
Above limit
Above limit
-
-
-
US - DC Contactor On
US - DC Contactor On
Same as
Same as "3-W ire
"Standard" except
Standard" except
it controls a DC
it controls a DC
contactor and
contactor and
requires a DC
requires a DC
contactor
contactor
acknowledge.
acknowledge.
3-Wire Standard*
-
-
-
-
-
-
-
-
Speed Reference
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Motor speed
Arm. voltage act.
Actual motor current
-
-
-
-
FixedSpeed1
-
-
External fault
External alarm
E-Stop
Reset
On Start pulse
Off1 Stop pulse NC
-
-
-
-
ReadyRun
ReadyRef (running)
Fault or alarm
Zero speed
Above limit
-
-
-
-
-
-
Main Contact. On
Drive turns on and
runs with pulsed
RUN input. It
turns off with
clearing of STOP
input (aka, 3-wire
control). Once
running, speed
changes to fixed
speed 1 (23.02)
when input DI-1 is
set, and returns to
run speed when it
is cleared. Run
speed is set with
AI-1.
5/30/2008