Pre-fuse the electric power supply in accordance with the power consumption of the air
conditioning system.
The air conditioning system may not be opened in hazardous classified locations unless
the environment has been known to be non-hazardous or power is switched off.
Repairs may only be carried out by the manufacturer or by a person appointed by the
manufacturer.
Modifications to the equipment or changes to the design are not permitted.
The product may only be used for the function for which it is designed and shall be
maintained in a good and clean condition.
An operating manual for the explosion-safe AR-051 series air conditioners is provided by
the original equipment manufacturer. Functionality is not changed by conversion of the
unit to explosion-safe.
If these instructions are not followed the explosion safety of the equipment cannot be
guaranteed. The equipment could then endanger the life of the user and could cause the
ignition of an explosive atmosphere. Consequently, Artidor as the manufacturer will waive
any responsibility.
3.
Characteristics
The characteristics can be summarized as follows:
Equipped with a connection box with cable glands and connection terminals.
Manufactured on the basis of European Directive 2014/34/EU (ATEX 114).
Suitable for use in gas hazardous areas classified as Zone 2.
Explosion safety category and protection against ignition applied (typical):
outdoor unit:
indoor unit:
remote control:
Protection degree against ingress of water and dust IP54.
4.
Application
The series AR-051 explosion-safe air conditioning units have been designed for and are
suitable for use in hazardous classified areas due to flammable gases, vapors and mist.
Because they are explosion-safe and certified on the basis of Group II Category 3 G of the
ATEX directive they are suitable for use in explosion hazardous areas classified as Zone 2.
If use in special environmental conditions is required, please contact the manufacturer
Artidor Explosion Safety B.V.
Installation manual AR-051 explosion-safe air conditioning systems
II 3 G Ex ec h ic mc IIC T3 Gc
II 3 G Ex ec h ic IIC T4 Gc
II 3 G Ex ic IIC T6 Gc
E
01-2020
5 / 40