ABB BT50 Manuel - Page 15
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} ABB BT50. ABB BT50 16 pages. Safety relay / expansion relay
12 Technical data
Manufacturer
Address
Power supply
Operational voltage
Power consumption
Relay outputs
Max. switching capacity
Resistive load AC
Inductive load AC
Resistive load DC
Inductive load DC
Max. total switching capacity
Min. load
Contact material
General
Fuses output (external)
Conditional short-circuit current
(1 kA)
Max. input wire res. at nom.
voltage
Response time
Degree of protection
Operating temperature range
Operating humidity range
Impulse Withstand Voltage
Pollution Degree
Weight
Colour
2TLC172316M0201, rev E
2015-09-30
ABB JOKAB SAFETY
Varlabergsvägen 11
SE-434 39 Kungsbacka
Sweden
+24 VDC +15 %/-25 %
< 2 VA
3 NO + 1 NC
6 A/250 VAC / 1500 VA
Utilization category AC-15: 240 VAC / 2 A
6 A/24 VDC / 150 W
Utilization category DC-13: 24 VDC / 1 A
12 A distributed on all contacts
10 mA/10 V (if load on contact has not exceeded 100 mA)
AgSnO2 + Au flash
5 A gL/gG
6 A gG
200 Ω
When deactivating
(input-output)
Enclosure
Connection blocks
-10°C to 55°C
35% to 85% (With no icing or condensation)
2.5 kV
2
200 g
Light grey and dark grey
15
<20 ms or delayed (BT50T) max 1500ms
IP 40 IEC 60529
IP 20 IEC 60529
www.abb.com/ jokabsafety