Ariston 110 L Manuel technique - Page 25

Parcourez en ligne ou téléchargez le pdf Manuel technique pour {nom_de_la_catégorie} Ariston 110 L. Ariston 110 L 39 pages. Heat pump water heater split

Ariston 110 L Manuel technique
PROGRAM mode: P1/P2/P1+P2
This mode can be selected only if enabled via installer menu (P11 Parameter ON).
Activating Program the device allows to reach the set delivery water temperature at the time
required, giving priority to heating by heat pump and, if necessary, through the heating element.
The final user can set two different programs with two different temperatures and times to be
performed separately (P1 or P2) or eventually together (P1+P2).
For this function is required the setting of the current time.
Note: To ensure comfort, in the case of P1 + P2 mode operation with very close times between
them, it is possible that the temperature of water is higher than the temperature set, in which
case it may appear the symbol of the waves.
Useful parameters:
Parameter
T
The desired temperature for P1 program.
set-point P1
Time_P1
The desired time for P1 program.
T
The desired temperature for P2 program.
set-point P2
Time_P2
The desired time for P2 program.
Installer menu parameter P3 - Adjustment of the maximum temperature obtainable
T
HP
with the heat pump unit.
The temperature of the water in the tank, to visualize press and release the knob;
T
water
the relative value will appear for 8 seconds then the set temperature will reappear.
Legend:
HP: Heat pump
HE: Electrical resistance (1200 W)
Case 1: T
T
set-point P1
Description/Functioning
HP
25
In this case the temperature
displayed is the next target to
reach.
Range
Default value
T
÷ T
55 °C
min
max
00:00 ÷ 23:59
06:00
T
÷ T
55 °C
min
max
00:00 ÷ 23:59
18:00
50 °C ÷ 62 °C
55 °C
-
-