S
TATUS AND FAILURE SIGNALIZATION
LED
color
indicators
green
"STATE"
yellow
"MENU"
O
PERATIONAL MODES
The level meters can either work in the "basic" mode that measures the level height (Fig. 17), or in
the "inverse mode" that measures distances (Fig. 18).
Fig. 17: Basic mode
(measurement of level height)
S
ETTING UP
After the level meter has been installed, set it up using the "DOWN" and "UP" buttons (see fi g. 16).
The LED indicator "MENU" indicates the on-going set-up procedure of the level meter. You can
set up the "basic mode", which measures the level height (Fig. 17) and set up the "inverse mode"
to measure distances (Fig. 18).
BASIC MODE :
Low margin (4 mA or 0 V) setting up
1.
The tank fi lls up to the level required
2.
Press the "DOWN" button for at least 2 seconds to activate the set-up mode (the LED indicator
"MENU" blinks slowly). Keep the "DOWN" button pressed for another 3 seconds to directly set the
value to 4 mA (0 V). In this case, item 3 can be omitted.
9
function
Slow fl ashing (1–2 sec., depends on the measuring interval) – reception of
refl ected signal (echo) from the measured level. Correct function.
Fast blinks – the measured value is in "dead zone" of the level meter, or the
ultrasonic transmitter is polluted.
Dark – the measured value is in "dead zone" of the level meter, or the
ultrasonic transmitter is polluted. Incorrect installation or malfunction.
Slow blinks – signalization setting limit 4 mA (0 V).
Fast blinks – signalization setting limit 20 mA (10 V).
Fig. 18: Inverse mode
(distance measurement)
ULM–53
© Dinel, s.r.o.