Ariston 200D Instructions pour l'installation, l'utilisation et l'entretien - Page 22

Parcourez en ligne ou téléchargez le pdf Instructions pour l'installation, l'utilisation et l'entretien pour {nom_de_la_catégorie} Ariston 200D. Ariston 200D 33 pages. Heat pump water heater

DEFAULT SETTINGS

The appliance is manufactured with a series of default modes, functions or values, as indicated in the table below:
PARAMETER
WORKING MODE
DEFAULT SET TEMPERATURE
MAX. TEMPERATURE SETTABLE WITH THE HEATING ELEMENT
MINIMUM SETTABLE TEMPERATURE
MAX. TEMPERATURE SETTABLE WITH THE HEAT PUMP
ANTIBACTERIAL FUNCTION
HOLIDAY MODE
DEFROST (active defrost activation)
HC-HP (two-tier rate operation mode)
HYSTERESIS
FAULTS
As soon as a fault occurs, the appliance enters into the fault mode while the display emits flashing signals and visualises the error code. The wa-
ter heater will continue supplying hot water if the fault affects only one of two the heating units, by activating the heat pump or heating element.
If the fault involves the heat pump, the symbol "HP" will flash on the screen, while the heating element symbol will flash if the fault involves it. If
both components are affected, both symbols will flash.
CAUTION!
Before intervening on the product by following the indications below, check the correct electrical connection of the components to the
mainboard and the correct position of the NTC sensors in their seats.
Cause
007
NTC Condenser: Open or Short Circuit
NTC Discharge (Compressor Outlet):Open or Short
008
Circuit
009
NTC Air: Open or Short Circuit
010
NTC Evap: Open or Short Circuit
012
NTC Suction (Compressor Inlet): Open or Short Circuit
021
Gas Leak
032
Compressor Issue
042
Evaporator Obstructed
044
Fan Issue
051
High Pressure
053
Compressor Thermal Protector: KO
081
Electronic Expansion Valve Issue
218
Dome NTC sensor (hot water): Open or Short Circuit
Water Temperature Sensor (Heating Element Zone):
230
Open or Short Circuit
Water Temperature sensor (Heating Element Zone):
231
safety intervention (1st level).
Water Temperature sensor (Heating Element Zone):
232
safety intervention (2nd level).
233
Relay blocked
314
ON / OFF repeated
321
Corrupted data
22 /EN
What to do
ON
OFF Verify NTC Condenser proper functioning
ON
OFF Verify NTC Discharge proper functioning
ON
OFF Verify NTC Air proper functioning
ON
OFF Verify NTC Evap proper functioning
ON
OFF Verify NTC Suction proper functioning
Verify compressor inlet sensor proper functioning. If the error persists,
ON
OFF
recover residual gas; find the leak in the cooling circuit; repair it; make
vacuum and recharge circuit with 1100g of refrigerant gas
ON
OFF Check power voltage on compressor connector.
Turn off the appliance.
ON
OFF
Check that the evaporator and the external unit casing is not obstructed.
Check power voltage on fan connector.
ON
OFF
Control the proper functioning of sensor at compressor inlet.
ON
OFF Check pressure switch wiring. Verify gas quantity.
ON
OFF Check compressor thermal protector connector.
Verify expansion valve cables. Verify NTC suction and NTC Evap correct
ON
OFF
functioning.
ON
OFF Verify NTC sensor (hot water) proper functioning
Check the correct assembly of sensor wiring on related mainboard
OFF
OFF
connector.
Verify sensor proper functioning.
OFF
OFF Verify sensor proper functioning.
OFF
OFF Verify sensor proper functioning.
Reset the appliance by pressing the ON/OFF button twice. If the error per-
OFF
OFF
sists, replace the motherboard.
OFF
OFF Wait 15 minutes before unlocking the product with ON/OFF button
Reset the product by pressing the ON / OFF button twice.
OFF
OFF
If the error persists, replace the motherboard.
FACTORY DEFAULT SETTING
GREEN
55 °C
75 °C
40 °C
62 °C
DEACTIVATED
DEACTIVATED
ACTIVATED
DEACTIVATED
12°C