Functions and Usage / Using
alarm, this port and the GND connecting (Low voltage), and the controller will stop working
and keep in alarm status.
6.7 Drive Failure
Over voltage or over current can lead the driver to a protected status, the drive will
automatically stop working, the motor stop and blue light is flashing. As long as you enable
terminal re-reset (EN and GND disconnected) or power Off, the driver will disarm the alarm.
When this failure occurs, please check the motor wire connection.
7. Using
Insure that motor line, hall line and power line connect correct, Motor and driver will be
damaged if lines connected wrong.
When using inner potentiometer speed adjust, connect "EN" with "GND" terminal,
connect SV terminal with 5V terminal, adjust speed by inner potentiometer.
When using external potentiometer to adjust speed: adjust R-SV to 1.0 position,
meanwhile connect EN to GND terminal, connect external potentiometer (middle
connection ) to SV terminal, the other two connect GND and +5V terminal.
Motor will running with highest speed under closed loop, adjust attenuation
potentiometer to get speed commanded.
page│7