4. 2. 1 Select Type of
Thermoregulation
To enabled
thermoregulation press
Auto button.
On the dispaly will appear
the symbol
4. 2. 2 Zone 1 Slope
°C
100
90
80
70
60
50
40
30
When an outdoor sensor is used, the boiler calculates the
most suitable delivery temperature, taking into account
the outside temperature and type of system.
The type of curve should be selected in correspondence
with the projected temperature of the system and the
nature of the dispersions present in the structure.
For high-temperature systems, one of the curves depicted
below may be chosen.
4. 2. 3 Parallel curve shift Zone
1 Off set
Auto Function active
To adapt the heating curve to the system requirements,
shift the curve in parallel so that the calculated fl ow
temperature is modifi ed, in addition to the room tempe-
rature.
By accessing the parameter and turning the encoder,
it is possible to shift the curve in a parallel direction.
The shifting value can be read on the display: from -14
to +14 for high-temperature devices, or from -7 to 7 for
low-temperature devices. Each step corresponds to a 1°C
increase/decrease In the fl ow temperature with respect to
the set-point value.
value
0 = Fixed Flow
Temperature
1 = Basic
Thermoreg.
2 = Room sensor
3 = Outdoor Temp.
only
4 = Room sensor +
outdoor Temp.
from 1.0 to 3.5
(high temperature)
from 0.2 to 0.8
(low temperature)
3.5
3.0
2.5
2.0
1.5
1.2
1.0
0.8
0.6
0.4
0.2
10
5
0
-5
-10
-15
-20 °C
External temperature
from - 14 to + 14 (°C)
(high temperature)
from - 7 to + 7 (°C)
(low temperature)
description
notes
1
4. 2. 4 Room sensor Infl uence
to calculate the set-
point temperature
- Thermoregulation
enabled-
If setted = 0 the room temperature doesn't infl uence the
calculation of the set-point.
If setted = 20, the room temperature has the maximun
infl uence to calculate the set-point
- only active when the BUS device is connected
4. 2. 5 Maximum Central Heating
1.5
Temperature Zone 1
0.6
4. 2. 6 Minimum Central Heating
Temperature Zone 1
4. 3 DIAGNOSTICS
4. 3. 4 Zone 1 heat request
5 ZONE 2 PARAMETER
5. 0 ZONE 2 TEMPERATURE SETTING
5. 0. 2 Fix temperature central
heating
To set only with Fixed Flow Temperaure of
Thermoregulation (see 521)
5. 2 ZONE 2 SETTING
5. 2. 0 Zone 1 Temperature range 0 = from 20 to 45°C
5. 2. 1 Select Type of
0
Thermoregulation
0
To enabled
thermoregulation press
Auto button.
On the dispaly will appear
the symbol
5. 2. 2 Zone 1 Slope
See parameter 422
Only enabled when an outdoor sensor is installed
When an outdoor sensor is used, the boiler calculates the
most suitable delivery temperature, taking into account
the outside temperature and type of system. The type
of curve should be selected in correspondence with the
projected temperature of the system and the nature
of the dispersions present in the structure. For high-
temperature systems, one of the curves depicted below
may be chosen.
technical area
value
from 0 to 20
20
from 35 to 85 °C
82
(Param. 420 = 1)
from 20 to 45 °C
45
(Param. 420 = 0)
from 35 to 85 °C
40
(Param. 420 = 1)
from 20 to 45 °C
25
(Param. 420 = 0)
0 = OFF
1 = ON
from 35 to 85 (°C)
70
(high temperature)
from 20 to 45 (°C)
25
(low temperature)
1
(low temperature)
1 = from 35 to 85°C
(high temperature)
0 = Fixed Flow
1
Temperature
1 = Basic
Thermoreg.
2 = Room sensor
3 = Outdoor Temp.
only
4 = Room sensor +
outdoor Temp.
from 1.0 to 3.5
1.5
(high temperature)
from 0.2 to 0.8
0.6
(low temperature)
35