Whirlpool 99044506A Instructions d'installation et manuel d'utilisation et d'entretien - Page 6

Parcourez en ligne ou téléchargez le pdf Instructions d'installation et manuel d'utilisation et d'entretien pour {nom_de_la_catégorie} Whirlpool 99044506A. Whirlpool 99044506A 28 pages. 30" (76.2 cm) and 36" (91.4 cm) range hood

Example vent system
90˚ elbow
2 ft (0.6 m)
Maximum Recommended Length
1 - 90° elbow
1 - wall cap
8 ft (2.4 m) straight
Length of 7" (17.8 cm) system
" x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
3 " x 10" (8.3 cm x 25.4 cm)
90° elbow
3 " x 10" (8.3 cm x 25.4 cm)
flat elbow
3 " x 10" (8.3 cm x 25.4 cm)
wall cap
Example vent system
3 " x 10"
(8.3 x 25.4 cm)
elbow
6 ft (1.8 m)
2 ft
(0.6 m)
Maximum Recommended Length
1 - 90° elbow
8 ft (2.4 m) straight
1 - wall cap
Length of 3 " x 10" (8.3 cm x 25.4 cm)
system
6
Wall cap
6 ft (1.8 m)
= 50 ft (15.2 m)
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
= 13.0 ft (3.9 m)
5.0 ft
(1.5 m)
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
Wall cap
= 35 ft (10.7 m)
= 5.0 ft (1.5 m)
= 8.0 ft (2.4 m)
= 0.0 ft (0.0 m)
= 13.0 ft (3.9 m)

Electrical Requirements

Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
If the house has aluminum wiring follow the procedure below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial rating plate.
The model/serial plate is located behind the filter on the rear
wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22. 1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.