Fire Control Panel – Sigma XT
SYSTEM ISOLATION
Rev 1.0
3. Isolation by Unplugging the FirePro Units
All FirePro Aerosol Generators are fitted with a Deutsch Plug. Unplugging the unit will
remove it from the System.
Ensure that all units are unplugged in the system as remaining units may be operational.
This will create a fault and operate "System Inoperative" signs.
Sigma_XT_Isol_1.0.Docx