Fireray 2000 Service et maintenance - Page 4
Parcourez en ligne ou téléchargez le pdf Service et maintenance pour {nom_de_la_catégorie} Fireray 2000. Fireray 2000 5 pages. Optical beam smoke detector
FIRERAY 2000
01B-05-S1
02
1/01
4.
ALIGNMENT
The detectors can be aligned by either using a dc voltmeter,
which is positioned at the Transmitter head and connected
via a 2-core cable to the Control Box or an Alignment Aid
which can be substituted for the voltmeter.
.
The Alignment Aid (Fig. 2) is lighter and more robust than a
meter and provides a convenient method of aligning the
detector heads. The display LED flashes at a faster rate when
correct alignment is achieved.
Align the detector heads as follows:
a) Switch on the 24V dc Supply to the Control
Box and the Transmitter/Detector.
b) Ensure the Test/Reset Switch on the Control
Box is set to OFF.
c) Set the Test/Reset Switch to ON.
d) Check the Signal Level control RV1 in the
Control Box is set to the mid-way position.
e) The High Gain (LED 3) and Low Gain
(LED 2) may both be lit.
Note: At this stage other LEDs in the Control Box may
be lit. This is due to the beams not being aligned
exactly.
f) Connect the Alignment Aid or dc voltmeter
as shown in Fig. 1 using 2-core cable.
PAGE 4 of 5
Fig. 2 Alignment Aid
g) Adjust the Transmitter head horizontally and
vertically so that the receiver detects the
beam in the round glass area such that either:
i) The Alignment Aid LED flashes at a high
rate - adjust for the fastest flashing rate.
ii) Or if using a voltmeter, adjust for a
maximum reading. (A no-signal reading
is approximately 2.6 volts).
h) When this has been done fully tighten the
screws holding the receiver and transmitter
to the ceiling brackets. Ensure that all
fixings are firmly tightened. Re-check the
alignment aid for faster flashing of the light
(to check the Beam Detector Set is working
correctly).
i) At the Control Box adjust RV1 until the
High Gain (LED 2) just goes off.
j) Switch off the power and disconnect the
Alignment Aid or voltmeter.
k) Set the Test/Reset switch to the off position.
Wait at least 45 seconds before performing
any tests.