TO COMMISSION DIRECT LOW PRESSURE
FIRETRACE SYSTEMS WITH ISOLATE VALVE
Warning Firetrace
cylinders contain 10.5 bar pressure
This procedure should be read in conjunction with document 006 basic design layout for
Direct Low Pressure systems with Isolate Valve.
Do not turn valve FT0117 until system is fully commissioned
Locate cylinder and firmly secure with bracket provided
Connect red Trace detection tube, tighten silver nuts and secure with appropriate clips
Remove gauge FT0107 from end of line gauge adapter FT0118
Fit Schrader adapter FT0172 and pressurise to 12 Bar / 175 psi using a nitrogen bottle or air
pump.
Remove Schrader adapter FT0172 and refit gauge FT0107
Check gauge is reading mid-green (same as cylinder gauge) and
leave system for a minimum
of ten minutes per metre of Trace detection tube to check for any leaks on the detection
tube.
When satisfied pressure is good and no leaks have occurred
open ball valve FT0117 slowly
System is now live
Optional FT0124 pressure switch can be fitted in spare gauge adapter
Open
Closed
on head assembly or at end of line
Please note system will not operate with isolate valve
in closed position