ABB RER103-MB Description technique - Page 5
Parcourez en ligne ou téléchargez le pdf Description technique pour {nom_de_la_catégorie} ABB RER103-MB. ABB RER103-MB 9 pages. Bus connection module
RER 103
2
6
Bus Connection Module
Technical Description
Principle of operation
The RER 103 Bus Connection Module can be used in Loop and Star type bus
topologies. Also the line idle state of the module is selectable. It can be light on or
off. The selection of Loop/Star and light on/off is made by jumpers.
In the Loop topology the RER 103 module passes a message received from the fibre-
optic interface both to the fibre-optic transmitter and the RS-485 interface.
In the Star topology the module passes a message received from the fibre-optic
receiver only to the RS-485 interface.
A message received from the RS-485 interface is passed to the fibre-optic
transmitter in both bus topologies.
SPA bus communication is using Loop and light off modes, when the module
jumpers are in Loop and light off positions. LON
and light off modes, when the module jumpers are in Star and light off positions.
IEC_103 bus communication is using Star and light on or off modes, when the
module jumpers are in Star and light on or off positions.
®
In LON
bus communication the RER 103 module supports collision detection. The
Service Pin is connected via the RS-485 interface to the Neuron
connected to the RER 103.
Fig. 2.-1 Rear side of the RER 103 module
Table 2.-1 Settings of the jumper
Topology
Light on/off
Star
Off
Star
Light
Loop
Off
Loop
Light
1MRS750532-MUM
®
bus communication is using Star
®
chip of the device
Protocol
LON or IEC 60870-5-103
IEC 60870-5-103
SPA
Not supported