Calex PMBXCF Manuel de l'opérateur - Page 15

Parcourez en ligne ou téléchargez le pdf Manuel de l'opérateur pour {nom_de_la_catégorie} Calex PMBXCF. Calex PMBXCF 17 pages.

Calex PMBXCF Manuel de l'opérateur
ACCESSING CONNECTED SENSORS VIA ANOTHER MODBUS MASTER
If the PM180 is connected to another Modbus Master, such as a Modbus PLC or SCADA, the
entire sub-network (the PM180, the connected sensors and output modules) appears as a
single Modbus Slave device to the PLC or SCADA. The Modbus Slave ID (Modbus Address) is
that of the PM180.
The temperatures and settings of the sensors connected to that PM180 can be read by
adding the following offsets to the sensor's own Modbus register addresses. The Sensor Index
is the position of the sensor in the PM180 sensor list. The Sensor Index numbers correspond
to the positions of the sensors on the PM180 screen as follows:
Sensor Index
0
1
2
3
4
5
Example
To read the Filtered Temperature on a PyroMiniBus sensor in position 4 on the PM180 as
shown above, read from register 0x0E + 0x1400 = 0x140E = decimal 5134.
For information on the Modbus addresses for other compatible sensors, please see the
Operator's Guide for that sensor.

MAINTENANCE

Our customer service representatives are available for application assistance, calibration,
repair, and solutions to specific problems. Contact our Service Department before returning
any equipment. In many cases, problems can be solved over the telephone. If the sensor is
not performing as it should, try to match the symptom below to the problem. If the table does
not help, call Calex for further advice.
GUARANTEE
Calex guarantees each instrument it manufactures to be free from defect in material and
workmanship under normal use and service for the period of two years from the date of
purchase. This guarantee extends only to the original buyer according to Calex Terms and
Conditions of Sale.
0
2
4
Address offset (hex)
0x1000
0x1100
0x1200
0x1300
0x1400
0x1500
1
3
5
Address offset (decimal)
4096
4352
4608
4864
5120
5376
15