Page 2 | Variable Speed Control

Connection Diagrams

2-Wire Controls with On/Off Switch
Mechanical Specifications (inches/mm) for P/N: 99 022
Mechanical Specifications (inches/mm) for P/N: 99 250 and 99 251
For more information, contact your Aldes sales advisor, visit aldes-na.com, call 1.800.255.7749, or find us on
©2020 American ALDES Ventilation Corporation. Variable Speed Control_Spec_and_IOM_1020. Aldes reserves the right to modify its products at any time to introduce new technologies.

Application Notes

1. Radio Frequency Interference (RFI): All solid-state
speed controls generate annoying radio noise on the AM
band. Speed controls contain, as standard, a high-gain
RFI suppression filter which significantly reduces this
interference.
2. Low-End Set Point (Minimum Speed): All 120 Volt input
speed controls are factory set to 60 Volts AC output (±3
Volts), as standard. All controls are factory calibrated using
an average responding AC voltmeter. Custom voltage
settings are available.
3. Motor Suitability: Motors must be loaded to nearly
full capacity with the appropriate fan blade in order to
achieve proper speed control. Generally, motor suitability
is established by determining motor speed as a function of
applied voltage. A motor is deemed suitable if it changes
speed linearly over a wide range of voltage. It is required
that all motors contain a built-in thermal overload
protector when used with solid-state speed controls.
4. Temperature Test: The non-sinusoidal output voltage of
a solid-state speed control may increase motor heating.
Therefore, it is necessary that a temperature test be
performed to ensure that the motor is operating within
manufacturer's specifications.
5. Leads: All leads are approximately 6" (15 cm) long and
stripped 1/2" (1.25 cm).

SAFETY WARNING!

Unit should be installed by a qualified electrician in accordance
with the National Electrical Code and other local codes which
may apply. This control must be grounded when installed.
Failure to follow these instructions may result in electrical
shock or a fire hazard. To reduce the risk of fire or electric shock,
this control is to be used only with fans marked as suitable for
use with solid state speed controls. This control is suitable for
mounting in a metal or polymeric field enclosure. These controls
must not be used at ratings exceeding those clearly marked on
the device.
We are not responsible for any expense, inconvenience or subsequent
damage caused by items of our manufacture or sale.
ISO 9001
2000 QMS