Parcourez en ligne ou téléchargez le pdf Installation Fonctionnement et entretien pour {nom_de_la_catégorie} aldes ZRT-IL. aldes ZRT-IL 4 pages. Airflow & zone controls in-line zone terminals

For units with optional wireless
communication relay, see
"Wireless Communication
Programming Supplement."
By replacing static grilles in large central
systems, the ZRT-IL-1 model provides on-
off control for on-demand ventilation. This
allows central fan downsizing and promotes
energy savings by minimizing necessary
fan horsepower and ventilation-induced
heat and cooling loads on the building. The
constant airflow regulator installed in the ZRT-
IL-1's extended duct collar places a maximum
flow limit on each terminal. The automatic
operation of the constant airflow regulator
will prevent noise and excessive energy
consumption caused by over-ventilation, as
well as fluctuations in airflow rates as total
system pressure varies.
The ZRT-IL-2 model can be used for
combination low-flow indoor air quality
ventilation and on-demand high-flow spot
ventilation using the same central fan system.
This is achieved by integrating a minimum
constant airflow regulator directly into the
damper sub-assembly. With the damper
completely closed, the factory-calibrated
constant airlfow regulator will still allow
steady, low-continuous ventilation during fan
operation. When other terminals are opened
for on-demand control of spot ventilation, the
closed ZRT-IL-2 will maintain the specified
low-continuous rate through the constant
airflow regulator minimum flow control. By
opening the ZRT-IL-2's control damper, the
low-flow regulator is removed from the air
stream, allowing either controlled (using
optional second constant airflow regulator)
or full maximum-boost ventilation.
The ZRT-IL can activate fans used in smaller
central ventilation systems. Through the use of
an integral damper end-switch, the ZRT-IL can
trigger the remote fan to start. This provides
the distinct advantage of allowing the fan
to only ventilate specific spaces when called
upon, without the need for separate fans in
each space. This is especially important in
residential bath applications using popular
in-line and multi-port fans, where low noise
and a single exterior vent penetration are
desired.
MOUNTING
The ZRT-IL includes a mounting bracket to
accommodate new or existing construction.
The versatile mounting options permit
FIGURE 1 - MOUNTING
ZRT-IL
Additional Screws
for Studs
Mounting Bracket
IMPORTANT:
Mounting
bracket must
be securely
anchored to joists.
TABLE 1 - SERVICE PARTS
Models with a Manufacture Date of December 2013 or Earlier
Damper Motor 24 VAC
Damper Motor 120 VAC
Damper Assembly 24 VAC for Models with 4" Duct Collar
Damper Assembly 24 VAC for Models with 6" Duct Collar
Damper Assembly 120 VAC for Models with 4" Duct Collar
Damper Assembly 120 VAC for Models with 6" Duct Collar
Models with a Manufacture Date of January 2014 or Later
Damper Motor 24 VAC
Damper Motor 120 VAC
Damper Assembly 24 VAC for Models with 4" Duct Collar
Damper Assembly 24 VAC for Models with 6" Duct Collar
Damper Assembly 120 VAC for Models with 4" Duct Collar
Damper Assembly 120 VAC for Models with 6" Duct Collar
installation above drop ceilings, between
ceiling joints, or within a small soffit location
(See Figure 1).
MAINTENANCE
Service parts are available. See Table 1.
WIRING
The ZRT-IL is available with 24 VAC or 120
VAC actuator motors. 120 VAC wiring options
are shown in Figures 2-4, and 24 VAC wiring
Dimples
Washers
Dimples
options using the Zone Terminal Fan Control
Center (Model ZTC) are shown in Figures 5
and 6.
WARRANTY
See enclosed warranty document.
2
ZRT-IL
Sheet Metal Screws
Washers
85 690
85 691
36 114
36 116
36 115
36 117
85 695
85 696
36 134
36 136
36 135
36 137