Acorn HFI-DPT-05 Manuel de démarrage rapide - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Acorn HFI-DPT-05. Acorn HFI-DPT-05 2 pages. Programming unit

IDENTIFIYNG THE DEVICE
Under the DevType and Addr captions on the programming unit's display, the connected analogue devices are visualized as per the follow-
ing table:
Device's type indication
Refers to...
Photo
Analogue and enhanced conventional smoke detector
PhtTherm
Analogue and enhanced conventional smoke and thermal detector
Thermal
Analogue and enhanced conventional thermal detector
I Module
Analogue input module or channel
O Module
Analogue relay output module or channel
OModSup
Analogue supervised output module or channel
Analogue multiple input / output channels device or analogue multi-
Multiple
module
CallPnt
Analogue call point
Sounder
Analogue sounder (wall or base)
Beacon
Analogue beacon
Sound B
Analogue sounder beacon
Conv Zon
Conventional zone module
Remote I
Analogue remote indicator lamp
Special
An analogue device that is not in this list
SETTING THE THERMAL OPERATING MODE
Having a detector with a thermal sensing feature connected to the programming unit, while visualizing ThrTyp on the main menu, press the
WRITE key: SelTyp (select type) caption will be displayed, and under it will be indicated either Std (standard ROR mode) or High°C (high
temperature mode) depending on the actual thermal operating mode of the detector; if you want to change the thermal mode just press UP
or DOWN to select the desired one, then press the WRITE key.
You can return to the main menu, if you decided not to change nothing, by pressing on the READ key.
SETTING THE OPERATING MODE VALUE
While in Set Mod / Set Op press the WRITE key. The Sel Op sub-menu and caption will appear on display: beneath it, three digits will
indicate the actual programmed operating mode value for the connected device that can be changed by pressing the UP or DOWN keys;
after the value has been chosen, just press WRITE to memorize it on the connected device.
You can return to the main menu, if you decided not to change nothing, by pressing on the READ key.
MESSAGES
The following table illustrates the most common messages given by the programming unit and their meaning:
Programming unit message
Meaning
Ent Test
This message is given when the enter test, made for the enhanced conven-
Error!
tional detector, failed
Ent Test
This message is given when the enter test, made for the enhanced conven-
Ok
tional detector, succeeded
An irreversible error; if this occurs, the detector is compromised, must not be
Fatal Error!
used and needs to be substituted
Storing
Indicates that the device is being programmed with the selected parameter
Indicates that the device has been successfully programmed with the selected
Stored
parameter
Reading
Indicates that the device is being queried for a parameter value
Read
Indicates that the device has been successfully queried for a parameter value
Failed
The performed reading or storing operation just failed
Miss Dev
No device is connected to the programming unit
BlankDev
The connected device has no firmware programmed
No Addr
The connected device has no analogue address
Low batt
Programming unit battery needs to be changed
Unspec
Customer security code is not specified
POWER OFF
The programming unit switches off by itself after 30 seconds of inactivity.
TECHNICAL SPECIFICATIONS
Power supply battery specifications
6LR61 type, 9 V
Operating temperature range
from -30°C to +70°C
Maximum tolerated relative humidity
95% RH (no condensation)
Weight
200 grams
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However,
after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by
external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced and
maintained on a regular basis to confirm correct operation.
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks.
Sensors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental condi-
tions.
Refer to and follow national codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manufacturing defects, effective from the
production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage.
Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified.
Full details on our warranty and product return policy can be obtained upon request.