Aerco 89030 Instruction technique - Page 5
Parcourez en ligne ou téléchargez le pdf Instruction technique pour {nom_de_la_catégorie} Aerco 89030. Aerco 89030 14 pages. Condensate neutralization tank
Condensate Neutralization Tank User Instructions
The condensate pump must be equipped with an over flow switch to prevent the appliance from
running should a failure occur. The over flow switch must be wired to the Remote Interlock of the
AERCO boiler/water heater I/O Box for KC1000, Innovation, and Benchmark units (see Figure 8);
or, for Modulex units, on Pins 3 and 4 of Connector I on Modulex E8 controller (see Figure 9).
NOTE:
For Modulex boilers, an over flow switch may only be utilized in Indoor/Outdoor Reset and
Constant Set Point modes of operation.
It cannot be utilized in 0 to 10 Volt Remote Set Point mode and when a BMS II is used.
To utilize an overflow switch, set the Modulex boiler to Standby mode (
to Standby mode, close the swing-down front panel door of the E8 and turn the wheel counter-
clockwise until the Standby symbol (
symbol, and others in the display, will be blinking. This indicates that the boiler is enabled.
When the connection is broken between pins 3 and 4, the Standby symbol, and others in the
display, will stop blinking indicating that the boiler is disabled. Closing/breaking pins 3 and 4
not only start/stops the boiler but also start/stops other pumps (boiler water pumps) wired to
the Modulex boiler.
•
TID-0074_0H
8/22/2022
) is displayed. With pins 3 and 4 closed, the Standby
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
). To set the boiler
Page 5 of 14