Installation & Operation Manual

PRELIMINARY STEPS

1. Read the installation instructions prior to beginning the installation.
2. Separate parts from packaging and verify all necessary parts are accounted for and undamaged. Obtain missing or
damaged parts from Acorn Safety prior to beginning installation.
3. Flush water supply lines prior to installation. This will remove unwanted debris from the lines and prevent unwanted
blockages in the safety equipment.
4. In order to comply with ANSI Z358.1, the safety equipment must be inspected periodically. An inspection tag is provided for
documentation purposes.
5. All employees at risk of contamination should be informed and trained in the use of this and any other safety equipment.
The signage provided should be posted appropriately in close proximity to this equipment.
S0704 ROUGH-IN
Per Application
8 5 8 "
Ø2 1 8 "
1-11 1/2" NPS
Mounting Hole
Size Ø1-3/8"
Acorn Safety
a division of Acorn Engineering
Manual #7109-508-001
5 1 8 "
6 1 2 "
Ø2 1 8 "
GENERAL NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM]
2. ANSI Z358.1 REQUIRES NOZZLES TO
BE BETWEEN 33" (838) AND 45" (1143) ABOVE
THE FLOOR.
Company
Page 2 of 8
1-11 1/2" NPS
Mounting Hole
Size Ø1-3/8"
2 Places
4"
Date: 03/28/13