1. APPLICATIONS
Control panel for 1 motor at 230 or 120 Vac depending on version, with integrated radio receiver.
2. OPERATING INSTRUCTIONS
Operations are carried out via button P.ALT (15-16) or with transmitters.
Operations can be finnished via any of the following: Activaiton by the corresponding the FC limit switch or by finalizing the working time.
If during opening, an order is given the operation will finish and the door will not close.
If during closing, an order is given the door will stop if another order is given the door will open.
Activation of C.SEG (13-14) during closing will open the door.
Activation of C.SEG1(12-13) during opening will stop the door (Option 3 OFF).
Activation of C.SEG1 (12-13) during opening and closing stops and inverts the door (Option 3 ON).
3. CONNECTIONS
3.2 TERMINAL CONNECTIONS
DEAD MAN
(OPTION 5 ON)
12 13
15 16
N.O
DEAD MAN
DEAD MAN
SAFETY CONTACT
CLOSE
OPEN
MONO 1H
Instructions MONO 1H
SAFETY EDGE
(OPTION 3 ON)
12 13
12 13
8K2 Ohm
N.C
SAFETY CONTACT
3.1 CONTROL PANEL
POWER
SUPPLY
1 2
230V
ACCESSORIES
SWITCHES
POWER SUPPLY
9 10
12V
MONOPHASE
MOTOR
3
4 5
M
MOTOR
LIMIT
SAFETY
12
6 7 8
13 14
LIMIT SWITCHES
SAFETY
CLOSE OPEN
CONTACTS
PUSH
BUTTONS
15 16
BOTÓN
ALT.
PHOTOCELL
TEST
11
0v
TEST
PHOTOC.
1 - 4