Safety devices

Delta
Connection for reopening during closing (N.C. contact). - With safety device such as photocells, sensitive safety-
edges and other devices. During closing, the contact triggers an inversion of movement until the gate is completely
open.
with DIP-switch 8 OFF - DIP-switch 2 OFF (Selector)
Connection for reclosing during opening (N.C. contact).
- With safety device such as photocells, sensitive safety-
edges and other devices. During the opening phases, the
contact triggers an inversion of movement until the gate is
completely closed.
Safety-test function connection - At each opening or closing command, the card verifies the photocells' efficiency. Any
malfunction in the photocells is singalled by theflashing LED on the control board, and cancels any command from the
radio transmitter or from the button.
IMPORTANT: Whenthe safety-test function is enabled, at least one pair of photocells must be connected to "reopen
during closing" (C1).
If unused, short-circuit 2-C1.
If unused, disable input CX with DIP-switch 8 set to ON.
with DIP-switch 10 ON
<- C1 ->
<- CX ->
with DIP-switch 8 OFF - DIP-switch2 ON (Selector)
Partial-stop connection (N.C. contact). - With safety
device such as photocells, sensitive safety-edges and
other devices. Stops movement and sets up for automatic
closing.
<- TS ->
Dir/DeltaS