Camille Bauer GOSSEN METRAWATT SINEAX TV 808-118 Manuel d'utilisation - Page 15
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Camille Bauer GOSSEN METRAWATT SINEAX TV 808-118. Camille Bauer GOSSEN METRAWATT SINEAX TV 808-118 20 pages. Isolating amplifier
(10)
(2)
(6)
Cami l l e Bauer AG
CH-561 0 Wohl e n
Swi t zerl a nd
ON
(12) (5)
(11)
Fig. 2
(2)
Front plate
(5)
Type label
(6)
Transparent cover
(7)
Fixing bracket
(8)
Opening for withdrawing clip (for opening the housing)
Top-hat rail 35 × 15 mm or 35 × 7.5 mm (EN 50 022)
(9)
(10)
Terminals
(11)
Terminals
(12)
Space for notes
ON
Green LED for indicating device standing by
6. Technical data
Measuring input
DC current:
Standard ranges 4...20 mA
Limit values
0...0.1 to 0...40 mA
also live-zero,
start value > 0 to ≤ 50% final value
– 0.1...0...+ 0.1 to
– 20...0...+ 20 mA
max. span: ≤ 40 mA
also bipolar asymmetrical
= 15 Ω
R
i
DC voltage:
Limit values
0...0.06 to 0...40,
also live-zero,
start value > 0 to ≤ 50% final value
– 0.06...0...+ 0.06 to
– 20...0...+ 20 V,
max. span: ≤ 40 V
R
= 100 kΩ
i
Overload:
(7)
(8)
(9)
Measuring output
DC current:
Burden voltage/
external resistance:
without
function
Current limiter at
ON
R
max.:
ext
Voltage limiter
= ∞:
at R
ext
Residual ripple in
output current:
Response time:
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 1: Nominal voltages and tolerances
Nominal voltage
U
N
24... 60 V
DC / AC
85...230 V
1
DC / AC
24... 60 V
DC / AC
85...230 V
AC
85...110 V
DC
1
For power supply > 125 V, the auxiliary circuit should include an
external fuse with a rating ≤ 20 A DC.
Power input:
Accuracy data (acc. to DIN/IEC 770)
Basic accuracy:
Installation data
Terminals:
Permissible vibrations: 2 g acc. to EN 60 068-2-6
DC current
continuously 2-fold
DC voltage
continuously 2-fold
Standard ranges
4...20 mA, 0 ... 20 mA
invert
20 ... 4 mA, 20 ... 0 mA
Standard version,
max. 1000 Ω
20 V / R
ext
Ex version,
max. 750 Ω
15 V / R
ext
Approx. 1.1 × I
AN
Approx. 26 V
< 0.5% p.p.
< 50 ms
Tolerance
Instruments
version
DC –15...+ 33%
Standard
AC ± 15%
(Non-Ex)
DC – 15...+ 33%
In
AC ± 15%
type of
± 10%
protection
intrinsically safe
[EEx ia] IIC
–15...+ 10%
≤ 1.2 W resp. ≤ 3 VA
Limit error ≤ ± 0.2%
Including linearity and reproduci-
bility errors
DIN/VDE 0609
Screw terminals with wire guards,
for light PVC wiring and
max. 2 × 0.75 mm
or 1 × 2.5 mm
2
2
15