4. Overview of the parts
Figure 3 shows those parts of the device of consequence for electrical
connections and other operations described in the Operating Instructions.
(6)
(4)
ON
(7)
(5)
(6)
Fig. 3
(4) Top-hat rail 35 × 15 mm or 35 × 7.5 mm (EN 50 022)
(5) Type label
(6) Terminals
ON Green LED to indicate the operating state and limit exceeded. The LED
flashes (option)
(7) Programming connector
5. Technical data
Measuring input
Input variable and measuring range configured
DC current:
Type 809 – xx1
Start value/final value between
– 100 and 100 mA, R
= 15.4 Ω
i
Any point may be zero
Type 809 – xx2
Start value/final value between
– 1.5 and 1.5 mA, R
= 1 kΩ
i
Any point may be zero
DC voltage:
EEx version max. 30 V
≤ ± 1.7 V, R
= 1 MΩ
i
> ± 1.7 to ≤ ± 100 V, R
= 540 kΩ
i
> ± 100 to ± 1000 V, R
= 5.5 MΩ
i
Reduced safety
Measuring output
DC current*:
Programmable,
reference range – 20 ... 20 mA,
start and final values anywhere within the
reference range, also with reversed direction
e.g. 20 ... 4 mA
External resistance:
R
max. ≤ 600 Ω with 20 mA output
ext
DC voltage*:
Programmable,
reference range – 10 ... 10 V,
start and final values anywhere within the
reference range, also with reversed direction
e.g. + 10 ... – 5 V
Load capacity:
R
min. ≥ 1000 Ω with 10 V output
ext
Programming connector on isolating amplifier
Interface:
Serial interface
Power supply
DC, AC power pack (DC or 45...400 Hz)
Rated voltages and permissible variations
Nominal voltage U
Tolerance
Instruments version
N
DC – 15...+ 33%
Standard
24... 60 V DC, AC
AC ± 15%
(Non-Ex)
85...230 V** DC, AC
DC – 15...+ 33%
Type of protection
24... 60 V DC, AC
AC ± 15%
"Intrinsic safety"
[EEx ia] IIC
85...230 V AC
± 10%
85...110 V DC
– 15...+ 10%
Power consumption:
≤ 1.2 W resp. ≤ 2.5 VA
Light emitting diodes
Green LED:
Light after switching on the power supply
Output contact
(Option)
Relay:
For monitoring the measured value limit.
1 galvanically isolated switching contact
Contact rating:
AC: ≤ 2 A / 250 V (500 VA)
DC: ≤ 2 A / 125 V (60 W)
Material:
Gold flashed silver alloy
Trip point type:
Programmable as low or high trip point
Trip point of measured variable
High trip point
Low trip point
G
S
GW
H
H
GW
S
G
H Hysteresis
GW Trip point
G Safe condition
S
Alarm condition
Fig. 4. Switching function,
according to trip point type.
Trip point adjustment
with PC for trip point:
Programmable between – 10 and 110%***
Hysteresis:
Programmable between > 0 and 100%***
Energizing and de-
energizing delays:
Programmable between 0 to 1080 s
Relay contact position:
Programmable
Frontplate signals:
The green LED "ON" flashes when the limit
value is exceeded
*
The type of output variable (current or voltage) is configurable with software
**
An external supply fuse must be provided for DC supply voltages > 125 V
*** In relation to the analog output value range
6. Mounting
The SINEAX TV 809 can be mounted on a top-hat rail.
When deciding where to install the isolating amplifier
(measuring location), take care that the limits of the
operating temperature are kept:
– 25 and + 55 °C
Simply clip the device onto the top-hat rail (EN 50 022) (see Fig. 5).
Fig. 5. Mounting onto top-hat rail 35 × 15 or 35 × 7.5 mm.
7. Electrical connections
The connections for the leads are fixed or plug-in screw terminals,
depending on the device execution. These are easily accessible at the
front of the isolating amplifier and are suitable for a wire cross-section of
max. 2.5 mm
2
.
Make sure that the cables are not live when making the
connections!
Impending danger by high input voltage or high
power supply voltage, 250 V at contact output.
2
Also note that, ...
... the data required to carry out the prescribed measurement must correspond to those marked on the nameplate of SINEAX TV 809
(
measuring input,
measuring output and
... the resistance in the output circuit may not overrange the current output value
12 V
R
max. [kΩ] =
ext
I
[mA]
AN
(I
= current output value)
AN
and not underrange the voltage output value
U
[V]
AN
R
min. [kΩ] ≥
ext
10 mA
(U
= voltage output value)
AN
... the measurement input and output cables should be twisted pairs and run as far as possible away from heavy current cables!
In all other respects, observe all local regulations when selecting the type of electrical cable and installing them!
In the case of "Intrinsically safe" explosion-proof, the supplementary information given on the type examination certifications,
the EN 60 079-14, and also local regulations applicable to electrical installation in explosion hazard areas must be taken into
account.
Measuring mode/application
DC voltage
Measuring range limits
≤ ± 1.7 V
> ± 1.7 to ≤ ± 100 V
+
–
–
1
2
3
= Measuring input
+
4
5
6
= Measuring output
K = Output contact
(Option)
= Power supply
8. Configuring the isolating amplifier
A PC, the programming cable PRKAB 600 (for Ex instruments) resp.
PRKAB 560 (for non-Ex instruments) plus ancillary cable and the
configuration software TV 800 plus are required to program the isolating
amplifier.
The connections between
"PC ↔ PRKAB 600 resp. 560 ↔ SINEAX TV 809" can be seen from
Fig. 6. The power supply must be connected in order to configure the
SINEAX TV 809.
The software TV 800 plus is supplied on a CD and runs under Windows
95 or higher.
The menu driven configuration software explains how to configure the
TV 809 and the choice of parameters.
The programming cable PRKAB 600 resp. PRKAB 560 adapts the signal
level and provides galvanic isolation between the PC and the SINEAX TV
809 isolating amplifier.
Continuation see on next page!
power supply)!
DC current
> ± 100 to ± 1000 V
≤ ± 100 mA
+
–
–
1
2
3
1
2
3
1
2
3
4
5
6
4
5
6
4
5
6
+
7
8
9
10 11 12
K
SINEAX TV 809
Ancillary cable
Interface
Programming
connector
Power supply
Fig. 6. Configuring a SINEAX TV 809, Ex version.
3
≤ ± 1.5 mA
PRKAB 600
COM