esera automation 11216 Manuel de l'utilisateur - Page 6

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} esera automation 11216. esera automation 11216 9 pages. 8-fold digital input for 1-wire bus
Également pour esera automation 11216 : Manuel de l'utilisateur (7 pages)

9
LED display and operating elements
The module has a green LED for each input channel, which lights up when a DC voltage greater than 10VDC is
applied. Input signals can be simulated via the two buttons. This can be helpful in case of service, during tests or
during commissioning. For the simulation, the LED displays and pushbuttons each have double functions.
Display
Designation
LED Green
PWR
LED Status
Status
1 – 8
LED Green
(8x)
Pushbutton Designation
Pushbutton 1
MAN/Select
Pushbutton 2
ON/OFF
10
Software / Control
The 1-Wire interface of the module is read out via 1-Wire command for the 1-Wire module DS2408.
The module is a standard module for very many systems and software programs, such as ESERA-Station 200,
PowerDog, SmartOne, FHEM, OWFS, IP-Symcon, etc
10.1
Data output 1-Wire Controller / 1-Wire Gateway
The 1-Wire interface of the 8-fold Digital Input is read by standard commands for the module DS2408.
For the 8-fold Digital Input, the following data is output for the binary / digital inputs. The input value is output as
decimal value 0-254 and in a second data set with binary display (0 and 1). Each input has a valence, which is
added up in each case.
Input value:
Input 1 = 1, input 2 = 2, input 3 = 4, input 4 = 8, input 5 = 16, input 6 = 32, input 7 = 64,
input 8 = 128.
Via the Config-Tool you can assign the article number 11216 to the DS2408 module. After assigning the article
number, you will receive the following formatted output.
Data output:
1_OWD1_1|8
1_OWD1_2|10000000
Further information about the possibilities and commands can be found in the current documentation 1-Wire
Controller /1-Wire Gateway.
*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de
Function
the LED has a double function
 lights up permanently, display for 12V power supply
 flashes in Manual Mode
the LED has a double function
 flashes when changing the input status of all inputs
 Manual Mode: input on/off for the selected channel
Status display of the inputs
 LED lights up when a signal voltage is applied to the corresponding
input.
 LED flashes if the input was set via the Manual Mode.
Function
the pushbutton has a double function
 press for 2 seconds, activation of Manual Mode for setting the inputs
 after that, selection of the input to be set by pressing briefly
the pushbutton has a double function
 input on/off in Manual Mode by pressing briefly
 press for 2 seconds, deactivates Manual Mode for all manually set
inputs
=> Controller No._module No._Data set | decimal value input
=> Controller No._module No._Data set | binary representation input
11216 V5.0 R1.0 Manual
Page 6 of 9