esera automation 11108 Manuel de l'utilisateur - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} esera automation 11108. esera automation 11108 4 pages. 5-fold distribution module for 1-wire temperature sensors

esera automation 11108 Manuel de l'utilisateur
3
Technical data
Output:
Input:
Display:
Operating voltage:
Current:
Protection circuits:
Temperature,operation: 0°C to +50°C
Air humidity:
Dimensions:
Protection class:
Housing protect.class:
4
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Interference immunity
EN 61000-6-3, interference radiation
RoHS
5
Connection 1-Wire network (input)
A screw connection for cable cross sections up to 2.5qmm is provided as input. The screw terminal can be
unplugged to mount the supply cable. For the electrical function only +5V, GND and Data are necessary.
Additionally a terminal for a 12V cable core is provided, this connection is not used internally.
6
Pin Assignment Output Sockets (RJ12) and Connection
The distribution module has 5 outputs with RJ12 sockets. Here 1-Wire cable temperature sensors can be
connected directly.
It is not necessary to remove the plugs, because the plugs of the temperature sensors are connected to the
1-Wire Extension 5 are coordinated.
The output sockets (RJ12 Western socket) are assigned as follows
Assignment RJ12 socket:
1
not connected
2
ground
3
1-Wire Data
4
1-Wire Data
5
+5 V
6
not connected
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
5 x RJ12 sockets (5V, GND und Data)
screw plug for cable to 2,5qmm
none
5 V= (+/-10%)
max. 100mA
ESD- and reverse polarity protection
10 - 92% (non condensing)
housing 90 x 50 x 25mm, mounting plate 120 x 55mm
III
IP20
11108 V1.0 R1.0 Manual
Page 2 of 4