ON 3 I-BEAMS
If continuous support is not possible, an alternative recommended support arrangement consists of 3 parallel I-
beams extending the full length of the unit: 2 supporting beams should be located along the unit length and 1 beam
should be located on the centreline of the unit. (see figure)
Each beam should be sized for 65% of the total operating weight. If a unit is installed on I-beams additional
insulation of the tank bottom is necessary to avoid the formation of condensation.
Installation on 3 I-beams
ON A ROOF
For installation of the unit on a roof, additional field insulation between tank bottom and the roof is required to
prevent condensation formation on the ceiling of the floor below (see figure). Recommended insulation material is a
vapour tight cork layer.
Installation on the roof
1. Cork layer
Rigging Method
RECOMMENDED LIFTING METHOD
The recommended method of rigging the unit is shown in the figure.