dixell CX620 Instructions d'installation et d'utilisation - Page 4
Parcourez en ligne ou téléchargez le pdf Instructions d'installation et d'utilisation pour {nom_de_la_catégorie} dixell CX620. dixell CX620 5 pages.
Également pour dixell CX620 : Instructions d'installation et d'utilisation (5 pages)
dIXEL
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
10. TTL/RS485 Serial line
The TTL connector allows, by means of the external module TTL/RS485 (XJ485CX), to connect the
unit to a network line ModBUS-RTU compatible as the dIXEL monitoring system XJ500 (Version
3.0). The same TTL connector is used to upload and download the parameter list of the "HOT KEY".
The instruments can be ordered wit the serial output RS485(Optional).
11. Use of the programming "HOT KEY "
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to
the "Hot Key" and vice-versa.
11.1 DOWNLOAD (FROM THE "HOT KEY" TO THE INSTRUMENT)
1.
Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present,
insert the "Hot Key" and then turn the Wing ON.
2.
Automatically the parameter list of the "Hot Key" is downloaded into the Wing memory, the
"DoL" message is blinking. After 10 seconds the instrument will restart working with the new
parameters.
3.
Turn OFF the instrument remove the "Hot Key", plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
"end " for right programming.
The instrument starts regularly with the new programming.
"err" for failed programming.
In this case turn the unit off and then on if you want to restart the download again or remove
the "Hot key" to abort the operation.
11.2 UPLOAD (FROM THE INSTRUMENT TO THE "HOT KEY")
1.
Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if
present; then turn it ON again.
2.
When the Wing unit is ON, insert the "Hot key" and push
appears.
3.
Push "SET" key to start the UPLOAD; the "uPL" message is blinking.
4.
Turn OFF the instrument remove the "Hot Key", plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
"end " for right programming.
"err" for failed programming. In this case push "SET" key if you want to restart the
programming again or remove the not programmed "Hot key".
12. ALARM SIGNALS
Message Cause
"P1"
Thermostat probe failure
"P3"
Probe 3 probe failure
"P4"
Probe 4 probe failure
"HA"
Maximum temperature alarm
"LA"
Minimum temperature alarm
"HA2"
Condenser high temperature
"LA2"
Condenser low temperature
"dA"
Door open
"EA"
External alarm
"CA"
Serious external alarm (i1F=bAL) All outputs OFF.
"CA"
Pressure switch alarm (i1F=PAL) All outputs OFF
"EE"
Data or memory failure
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the "P1" which is
flashing.
To reset the "EE" alarm and restart the normal functioning press any key, the "rSt" message is
displayed for about 3s.
12.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing any key. Buzzer is mounted
in the keyboard and it is an option.
12.2 "EE" ALARM
The dIXEL instruments are provided with an internal check for the data integrity. Alarm "EE" flashes
when a failure in the memory data occurs. In such cases the alarm output is enabled.
12.3 ALARM RECOVERY
Probe alarms : "P1" (probe1 faulty), "P3" and "P4"; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe.
Temperature alarms "HA", "LA" "HA2" and "LA2" automatically stop as soon as the temperature
returns to normal values.
Alarms "EA" and "CA" (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm "CA" (with i1F=PAL) recovers only by switching off and on the instrument.
13. Technical data
Keyboards
Housing: self extinguishing ABS.
Case: T620: facia 38x185 mm; depth 23mm
V620: facia 72x56 mm; depth 23mm
CX620: facia 75x36 mm; depth 23mm
Mounting: T620: panel mounting in a 150x31 mm panel cut-out with two screws.
Distance between the holes 165mm
V620: panel mounting in a 56x72 mm panel cut-out with two screws.
between the holes 40mm
CX620: panel mounting in a 71x29mm panel cut-out
1592026000 XW20K GB R1.0 22.02.2008.doc
Installing and Operating Instructions
o
key; the "uPL" message
Outputs
Alarm output ON; Compressor output according to
parameters "COn" and "COF"
Alarm output ON; Other outputs unchanged
Alarm output ON; Other outputs unchanged
Alarm output ON; Other outputs unchanged
Alarm output ON; Other outputs unchanged
It depends on the "Ac2" parameter
It depends on the "bLL" parameter
Compressor and fans restarts
Output unchanged.
Alarm output ON; Other outputs unchanged
∅
3x2mm. Distance
Protection: IP20; Frontal protection: IP65 with frontal gasket
Connections: Screw terminal block
Power supply: from XW20K power module
Display: 3 digits, red LED, 14,2 mm high.
Optional output: buzzer
Power module XW20K
Case: 8 DN: 140X176X148.
Connections: Screw terminal block
Power supply: 230Vac or. 110Vac
Power absorption: 10VA max.
Inputs: 4 NTC probes
Digital inputs: 1 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light (oA3): relay SPST 16(5) A, 250Vac
Serial output : TTL standard.
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
14. CONNECTIONS
14.1 XW20K
15. Default setting values
Label Name
REGULATION
Set Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
Ot
Thermostat probe calibration
P3P Third probe presence (1st cond.
probe)
O3
Third probe calibration
P4P Fourth probe presence (2nd
probe)
O4
Fourth probe calibration
OdS Outputs activation delay at start up
AC Anti-short cycle delay
Ac1 Second compressor delay
CCt Compressor ON time during fast
freezing
CCS Set point for continuous cycle
COn Compressor ON time with faulty probe
COF Compressor OFF time with faulty
probe
CH Kind of action
DISPLAY
CF
Temperature measurement unit
rES Resolution (integer/decimal point)
rEd Remote display
dLy Display temperature delay
DEFROST
dFP Probe selection for defrost termination
dtE Defrost termination temperature
IdF Interval between defrost cycles
MdF (Maximum) length for 1° defrost
dFd Displaying during defrost
dAd MAX display delay after defrost
AUXILIARY THERMOSTAT
ACH Kind of action for auxiliary relay
SAA Set Point for auxiliary relay
SHy Differential for auxiliary relay
3 x 2mm.
∅
ArP Probe selection for auxiliary relay
Sdd Aux.output working during defrost
ALARMS
XW20K
2,5 mm
≤
2
2,5 mm
heat-resistant wiring and 6,3mm Faston
≤
2
10% or 24Vac
±
÷
85% (no condensing)
Range
LS÷US
0,1÷25,5 °C / 1÷45°F
-50,0°C÷SET / -58°F÷SET
SET ÷ 110°C / SET ÷ 230°F
-12÷12°C /-120÷120°F
n=not present; Y=pres.
-12÷12°C /-120÷120°F
cond.
n=not present; Y=pres.
-12÷12°C /-120÷120°F
0÷255 min.
0÷30 min.
0÷255s
0 ÷ 23h 50 min.
(-55.0÷150,0°C)
0÷255 min.
0÷255 min.
CL=cooling; Ht= heating
°C ÷ °F
in ÷ de
P1 ÷ 1r2
0 ÷ 20.0 min (10 sec.)
nP; P1; P2; P3; P4
-50,0÷110°C / -58÷230°F
1÷120h
0÷255 min.
rt, it, SEt, dEF, dEG
0÷255 min.
CL; Ht
-50,0÷110°C / -58÷230°F
0,1÷25,5 °C / 1÷45°F
nP / P1 / P2 / P3
1592026000
Default Level
3.0
- - -
2.0
Pr1
-50.0
Pr2
110
Pr2
0.0
Pr1
n
Pr2
0
Pr2
n
Pr2
0
Pr2
0
Pr2
1
Pr1
5
Pr2
0.0
Pr2
3
Pr2
15
Pr2
30
Pr2
cL
Pr1
°C
Pr2
dE
Pr1
P1
Pr2
0
Pr2
nP
Pr2
0
Pr2
8
Pr1
20
Pr1
it
Pr2
30
Pr2
cL
Pr2
0,0
Pr2
2,0
Pr2
nP
Pr2
n, y
n
Pr2
4/5