dixell COOL MATE XLR470 Manuel d'utilisation - Page 16
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} dixell COOL MATE XLR470. dixell COOL MATE XLR470 18 pages. Dual temperature controller
dIXEL
dIXEL
dIXEL
dIXEL
17.
DEFAULT SETTING VALUES
Label
REGULATION
Set1
Set point 1
Set2
Set point 2
Hy1
Differential 1
Hy2
Differential 2
REGULATION – SECTION 1
LS1
Minimum set point1 limit
US1
Maximum set point1 limit
odS1
Outputs activation delay of sect. 1 at start up
Ac1
Anti-short cycle delay for compressor1
con1
Compressor1 ON time with faulty probe1
coF1
Compressor1 OFF time with faulty probe1
cH1
Kind of action for section 1
REGULATION – SECTION 2
LS2
Minimum set point2 limit
US2
Maximum set point2 limit
odS2
Outputs activation delay of sect. 2 at start up
Ac2
Anti-short cycle delay for compressor2
con2
Compressor2 ON time with faulty probe2
coF2
Compressor2 OFF time with faulty probe2
cH2
Kind of action for section 2
DISPLAY
cF
Temperature measurement unit
rES
Resolution (for °C
Lod1
Bottom display visualization
Lod2
Upper display visualization
DEFROST
dFS
Relation between defrosts
tdF1
Kind of defrost section 1
EdF1
Defrost mode, section 1
SdF1
Set point for Smart Defrost section 1
dtE1
End defrost temperature section 1
idF1
Interval between defrosts, section 1
MdF1
Maximum duration of defrost, section 1
tPF1
Pre-defrost compressor on time
Fdt1
Dripping time section 1. 1
dPo1
Defrost at power on section . 1
tdF2
Kind of defrost section 2
EdF2
Defrost mode, section 2:
SdF2
Set point for Smart Defrost section 2
dtE2
End defrost temperature section 2
idF2
Interval between defrosts, section 2
MdF2
(Maximum) duration of defrost, section 2
tPF2
Pre-defrost compressor 2 on time
Fdt2
Dripping time section 2
dPo2
Defrost at power on section 2
dFd
Display during defrost
dAd
Defrost display time out
dSd
Defrost delay
FANS
FnC1
Fans operating mode, section 1
Fnd1
Fans delay after defrost, section 1
FSt1
Fans stop temperature, section 1
FAP1
Probe for fans
FnC2
Fans operating mode, section 2
Fnd2
Fans delay after defrost, section 2
1592017050 XLR470 GB r1.0 24.05.07.doc
Operating manual
Name
Range
LS1÷US1
LS2÷US2
0,1÷25,5 °C / 1÷45°F
0,1÷25,5 °C / 1÷45°F
-50,0°C÷SET1 / -58°F÷SET1
SET1 ÷ 150°C / SET1 ÷ 302°F
0÷255 min.
0÷30 min.
0÷255 min.
0÷255 min.
cL / Ht
-50,0°C÷SET2 / -58°F÷SET2
SET2 ÷ 150°C / SET2 ÷ 302°F
0÷255 min.
0÷30 min.
0÷255 min.
0÷255 min.
cL / Ht
°C / °F
in ÷ de
P1 ÷ P4
P1 ÷ P4
ind; StS; Sti, SE
rE, in
In, Sd,RTC
-30 ÷ +30°C / -22÷+86°F
-50,0÷110°C/ -58÷230°F
1÷120ore
0÷255 min.
0÷30 min.
0÷60 min.
n ÷ y
rE, in
In, Sd, RTC
-30 ÷ +30°C / -22÷+86°F
-50,0÷110°C/ -58÷230°F
1÷120ore
0÷255 min.
0÷30 min.
0÷60 min.
n ÷ y
rt, it, SEt, dEF, dEG
0÷255 min.
0÷255 min.
C-n, C-y, O-n, O-y
0÷255 min.
-50,0÷110°C/ -58÷230°F
P1÷P3
C-n, C-y, O-n, O-y
0÷255 min.
XLR470
cod. 1592017
cod. 1592
cod. 1592
cod. 1592
017
017050
017
050
050
050
Default
level
-5.0
- - -
3.0
- - -
2.0
Pr1
2.0
Pr1
-50.0
Pr2
110
Pr2
0
Pr2
1
Pr1
15
Pr2
15
Pr2
cL
Pr2
-50.0
Pr2
110
Pr2
0
Pr2
1
Pr1
15
Pr2
15
Pr2
cL
Pr2
° C
Pr2
dE
Pr1
P1
Pr2
P3
Pr2
ind
Pr2
rE
Pr2
in
Pr2
0
Pr2
8.0
Pr2
6
Pr1
20
Pr1
0
Pr2
0
Pr2
n
Pr2
rE
Pr2
in
Pr2
0
Pr2
8.0
Pr2
6
Pr1
20
Pr1
0
Pr2
0
Pr2
n
Pr2
it
Pr2
20
Pr2
0
Pr2
O-n
Pr2
10
Pr2
2.0
Pr2
P2
Pr2
O-n
Pr2
0
Pr2
16/18