Dixon Bayco FloTech FT208 Manuel - Page 11

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Dixon Bayco FloTech FT208. Dixon Bayco FloTech FT208 20 pages. Checkmate programmable retain / overfill onboard monitor

Another Socket Option is to install the FloTech FT390 Dual Socket Assembly. This unit comes with the
sockets pre-wired to a length of FloTech eleven conductor cable. Refer to Fig. 9 for wiring connections.
TB2 AUX PERMIT Connections
Refer to Fig. 10. In order for the FT208 Monitor to work properly, the AUX terminals must be connected
together. This can be done either by placing a shorting jumper across the AUX terminals (factory installed) or
by connecting the AUX terminals to a dry relay contact. Examples of this would be a Hobbs switch or a Vapor
Recovery interlock switch. When the AUX connection is made, the FT208 Monitor issues a PERMIT signal.
TB2 RETAIN RESET Connections
Refer to Fig. 10. The Retain Reset terminals connect to a Normally Open push button switch. The primary
function of this switch is to override wet Retain Sensors for 'Splash Blending' product. When this button is
pressed, the FT208 Monitor will issue a Permit signal to the Rack without regard to the Retain Sensors. The
Permit signal will be disabled if any of the Overfill Sensors become wet or there is signal activity on any Retain
Sensors that have been programmed as inactive.
FloTech Programmable CheckMate Retain / Overfill Monitor
Optic Socket Connections
FloTech FT390 Series Socket Connections
FT208 CheckMate
Fig. 8
Fig. 9
10466 REV N
11